Typical Limiting Values of SubStation Equipments

 

Typical Limiting Values of Sub Station Electrical Equipments.

1. Transformer / Reactor:

Sr. No.Equipment / test dataPermissible limitsReference
A)Transformer oil  
a) BDV  
-At the time of first charging600 kV (Gap – 2.5 mm) – MinimumIS – 1866
-During O&M50 kV (Gap – 2.5 mm) – MinimumIS – 1867
b) Moisture content IS – 1868
-At the time of first charging15 PPM (Max.)IS – 1869
-During O&M25 PPM (Max.)IS – 1870
c) Resistivity at 90 degree C0.1-1012 Ohm-CM (Min.)IS – 1871
d) Acidity0.2 mg KOH/gm (Max.)IS – 1872
e) IFT at 27 degree C0.018 N/M (Min.)IS – 1873
f) Tan delta at 90 degree C0.20 (Max.)IS – 1874
g) Flash point126 Deg. C (Min.)IS – 1875
B)Vibration level for reactors200 Microns (Peak to Peak)IS – 1876
 60 Microns (Average)IS – 1877
C)Tan delta for bushing at 20 Deg. C0.007*IEC – 137
D)Capacitance for bushing+ 5% variationIEC – 138
E)IR value for winding1000 M-Ohm By 5.0/10.0 kV MeggerIEC – 139
F)Tan delta for windings at 20 Deg. C0.007*IEEE/C57.12.90.1980
G)Contact resistance of bushing terminal connectors10 M. Ohm / ConnectorNGC.UK Recommendations
H)Turret Neutral CT ratio errors39IS – 2705

 2. Circuit Breakers 

Sr. No.Equipment / test dataPermissible limitsReference
A)Dew point of SF6 gasDew point values as per Annexure – II 
B)Dew point of operating air-45 Deg. C at ATM. Pressure 
C)CB Operating timings400 kV               220KV 
a) Closing time (Max.)150 MS              200MS 
b) Trip time (Max.)25 MS                35MS 
c) Close/trip time, Pole discrepancy  
– Phase to Phase (Max.)3.33 MS            3.33MS 
-Break to break (Max.) of same phase2.5 MS              2.5MS 
D)PIR time  
BHEL make12-16 MSManufacturers Recommendations
   
ABB make8-12 MSManufacturers Recommendations
NGEF make8-12 MSManufacturers Recommendations
M&G make8-12 MSManufacturers Recommendations
TELK make8-12 MSManufacturers Recommendations
ABB make (HVDC)8-12 MSManufacturers Recommendations
E)PIR opening time prior to opening of main contacts (ABB, CGL, NGEF make CBs)5 MS (Min.) at rated pressureManufacturers Recommendations
F)Pir and main contacts overlap time [BHEL, M&G, ABB (imported) make CBs]6 MS (Min.) at rated pressureManufacturers Recommendations
G)Tan delta of grading capacitors0.007 at 20 Deg. C 
H)Capacitance of grading capacitorsWithin + 10% / -5% of the rated valueIEC 359
I)Contact resistance of CB150 M. Ohm 
J)Contact resistance of CB terminal connector10 M. Ohm per connectorNGC, UK recommendations
K)IR value:  
1. Phase – earth1000 M Ohm (Min.) by 5.0 / 10.0 kV Megger 
2. Across open contacts1000 M Ohm (Min.) by 5.0/10.0 kV Megger 
3. Control cables50 M Ohm (Min.) by 0.5 kV Megger 
L)Pressure switch settings  
-SF6 gas pressure switchesWithin + 0.1 Bar of set value 
-Operating air pr. SwitchesWithin + 0.1 Bar of set value 
-Operating oil pr. SwitchesWithin + 0.1 Bar of set value 
M)BDV of oil used for MOCB  
-At the time of filling40 kV at 2.5 mm Gap (Min.)Mfgs. Recommendation
-During O&M20 kV at 2.5 mm Gap. (Min.)Mfgs. Recommendation

 3. Current Transformer

Sr. No.Equipment / test dataPermissible limitsReference
A)IR value  
1. Primary – earth1000 M – Ohm (Min.) by 5.0/10.0 kV Megger 
2. Secondary – earth50 M – Ohm (Min.) by 0.5 kV Megger 
3. Control cables50 M-Ohm (Min.) by 0.5 kV Megger 
B)Tan delta value0.007* at 20 Deg. C 
C)Terminal Connector10 M-Ohm per connectorNGC, UK Recommendations
D)CT ratio errors+ 3% -Protection coresIS – 2705
D)CT ratio errors+ 1% -Metering coresIS – 2706

 4. Capacitive Voltage

Sr. No.Equipment / test dataPermissible limitsReference
A)Tan Delta0.007* at 20 Deg. C 
B)CapacitanceWithin +10%/-5% of the rated valueIEC – 358
CContact resistance of terminal connector10 M-Ohm per connectorNGC, UK Recommendations
D)IR ValueIR Value 
1. Primary – earth1000 M – Ohm (Min.) by 5.0/10.0 kV Megger 
2. Secondary – earth50 M – Ohm (Min.) by 0.5 kV Megger 
3. Control cables50 M-Ohm (Min.) by 0.5 kV Megger 
E)EMU tank oil parametersEMU tank oil parameters 
a) BDV (Min.)30 kV (Gap. –2.5 mm)IS – 1866
b) Moisture content (Max.)35 ppm-do-
c) Resistivity at 90 Deg. C0.1 – 1012 Ohm. – CM-do-
d) Acidity0.5 mg kOH /gm (Max.)-do-
e) IFT at 27 Deg. C0.018 N/M (Min.)-do-
f) Tan delta at 90 Deg. C1.0 Max.-do-
g) Flash point125 Deg. C (Min.)-do-
F)CVT voltage ratio errors+ 5% protection coresIEEE/C93.1.1990
F)CVT voltage ratio errors+ 0.5% metering coresIEC 186

 5. Isolators

Sr. No.Equipment / test dataPermissible limitsReference
A)Contact resistance300 M-Ohm. (Max.) 
B)Contact resistance of terminal connector10 M – Ohm per connectorNGC, UK Recommendations
C)IR value  
1. Phase – earth1000 M – Ohm (Min.) by 5.0/10.0 kV MeggerNGC, UK Recommendations
2. Across open contacts1000 M – Ohm (Min.) by 5.0/10.0 kV MeggerNGC, UK Recommendations
3. Control cables50 M-Ohm (Min.) by 0.5 kV Megger 

 6. Surge Arrester

Sr. No.Equipment / test dataPermissible limitsReference
A)Leakage current500 M-Amp. (Resistive)Hitachi, Japan Recom.
B)IR value1000 M-Ohm. (Min.)Hitachi, Japan Recom.

 7. Miscellaneous

Sr. No.Equipment / test dataPermissible limitsReference
A)Station earth resistance1.0 Ohm (Max.) 
B)Thermo vision scanning  
Temp. up to 15 Deg. C (above ambient)Normal 
Temp. above 15-50 Deg. C (above ambient)Alert 
Temp. above 50 Deg. C (above ambient)To be immediately attended 
C)Terminal connectors – Contact resistance10 M-Ohm per connectorHGC, UK Recommendations
D)IR values  
1. All electrical motors50 M-Ohm (Min.) by 0.5 kV Megger 
2. Control cables50 M-Ohm (Min) by 0.5 kV Megger 
3. Lt. Transformers100 M.-Ohm (Min.) by Megger 
4. Lt. Switchgears100 M – Ohm (Min.) by 0.5 kV Megger 

 8. Batteries

Sr. No.Equipment / test dataPermissible limitsReference
A)Terminal connector resistance10 M – Ohm + 20%ANSI/IEEE – 450 1989
B)Specific gravity1200 + 5 GM/L at 27 Deg. C 

 Temperature Correction Factor for Tan Delta Measurement

 Sr. No. Oil temperature Deg. C Correction factor(K)
 1 10 0.8
 2 15 0.9
 3 20 1.0
 4 25 1.12
 5 30 1.25
 6 35 1.40
 7 40 1.55
 8 45 1.75
 9 50 1.95
 10 55 2.18
 11 60 2.42
 12 65 2.70
 13 70 3.00

If Tan Delta of bushing/winding/CVT/CT is measured at oil temperature T Deg. C. Then Tan Delta at 20 Deg. C shall be as given below:

Tan Delta at 20 Deg. C = Tan Delta at Temp T Deg. C / Factor K.

Dew Point Limits for SF6 Gas in EHV Circuit Breakers

Sr. NoMake of C.BDew point at rated Pr. Deg. C Corresponding dew point at Atmospheric .Pr. Remarks
1BHEL  -15 -36 At the time of commissioning
 -7 -29 During O&M
 -5 -27 Critical
2M&G — -39 At the time of commissioning
  -32 During O&M
3CGL -15 -35 At the time of commissioning
 -10 -31 During O&M
4ABB -15 -35 At the time of commissioning
 -5 -26During O&M
5NGEF -15 -36At the time of commissioning
 -7 -29 During O&M

 Note: Dew point of SF6 gas varies with pressure at which measurement is carried out. So it is to be ensured that if measurement is done at pressure other than atmospheric pressure, it needs to be converted to the atmospheric pressure.