Quick Reference-Fire Fighting (Part-2)

 

Size of the Mains for Fire Fighting as per Type of Building ( IS 3844 )

Mains of Fire FightingType of BuildingBuilding Height
100 mm single outlet landing valvesI) Residential buildings (A)
a) Lodging housing15 Meter to 45 Meter
b) Dormitory15 Meter to 45 Meter
c) Family private dwellings15 Meter to 45 Meter
d) Apartment houses15 Meter to 45 Meter
e) With shopping area not exceeding 250 m215 Meter to 45 Meter
f) Hotel buildings up to 3 star grade15 Meter to 24 Meter and area not exceeding 600 m2 per floor
100 mm single outlet landing valvesII) Educational buildings (B) Above 15 m but not exceeding 35 m
101 mm single outlet landing valvesIII) Institutional buildings (C) Above 15 m but not exceeding 35 m
100 mm single outlet landing valvesa) For hospitals and sanatorium with beds not exceeding 100no’sAbove 15 m but not exceeding 25 m
100 mm single outlet landing valvesb) For custodial places and mental institutions Above 15 m but not exceeding 35 m
100 mm single outlet landing valves IV) Assembly buildings (D)Above 15 m but not exceeding 24 m and total floor area not exceeding 500 m2/floor
100 mm single outlet landing valvesV) Business buildings (E)Above I5 m but not exceeding 24m
100 mm single outlet landing valvesVI) Mercantile buildings (F) Above 15m but not exceeding 24 m
100 mm single outlet landing valvesVII) Industrial buildings (G)Above 15 m but not exceeding 24 m
150mm with twin outlet landingVIII) All buildings classified  under(I) To (IV) Above 45 m
150mm with twin outlet landing IX) All buildings classified  under( v) above with shopping area not exceeding 250 m2 Above 24 m
150mm with twin outlet landingX) All buildings classified under (vi) aboveAbove 24 m and area exceeding 600 m2
150mm with twin outlet landingXI) Hotel buildings of  4 star and 5 star gradeAbove 15 m
150mm with twin outlet landingXII) All buildings classified under II and III aboveAbove 25 m/35 m as applicable
150mm with twin outlet landingXIII) All buildings classified under IV aboveAbove 25 m and area exceeding 500m2/floor
150mm with twin outlet landingXIV) All buildings classified under V aboveAbove 24 m
150mm with twin outlet landingXV) All buildings classified under VI aboveAbove 24 m but not exceeding 35 m
150mm with twin outlet landingXVI) All buildings classified under VII aboveAbove 24 m but not exceeding 35 m
150mm with twin outlet landingXVII) All storage buildings (H)Above 10 m but not exceeding 24 m

 

As per (IS 3844)

Type of RiserInternal hydrants form part of any of the following systems
a) Dry-riser system,
b) Wet-riser system,
c) Wet-riser-cum-down-comer system
d) Down-comer system.
Dry-Riser System ( for Cold Region )Dry-riser main system can be installed in buildings under Group A (iI, ii, ii, iv ), where the height of building is above 15 m but not exceeding 24 m up to terrace level and where the water supply for firefighting is immediately available either through the underground water storage tank/tanks or through water mains/town’s main
Dry-riser system does not include hose reel, hose cabinets, fire hose and branch pipes.
Wet-Riser SystemWet-riser system should be provided in the types of buildings according to the provision mentioned. The system should consist of a pipe or  number of pipes depending on the area and height of the buildings permanently charged with water under pressure with landing valves, hose reel, hose, branch pipe, etc, at every floor level
A provision of pressure differential switch to start the pump automatically, so that water under pressure is advisable for operational hydrant, hose reels, etc, as soon as the water is drawn from hydrant landing valves causing drop in pressure. The system also incorporates a stand-by pump to come into operation automatically when the normal power supply source fails.
The distribution of wet-riser installation in the building should be so situated as not to be farther than 30 m from any point in the area covered by the hydrant and at a height of 0.75 m to 1 m from the floor. The rising mains should not be more than 50 m apart in horizontal.
Fire service inlet with gate and non-return valve to charge the riser in the event of failure of the static pump directly from the mobile pump of the tie services should: be provided on the wet-riser system. The, fire service inlet for 100 mm internal diameter rising main should have collecting head with 2 numbers of 63 mm inlets and for 150 mm rising main, collecting head with 4 numbers of 63 mm inlets should be provided.
For wet-risers down-comer system, two pumps of different capacities one for the wet-riser and the other for down-comer system should be installed. The pumps should be fed from normal source of power supply and also by an alternative source in case of failure of normal source.
For a wet-riser system, two automatic pumps should be installed to independently feed the wet riser main, one of which should act as stand-by, each pump being supplied by a different source of power. The pump shall be arranged so that when acting as duty-pump, operate automatically when one or more hydrant is opened thus causing a drop in pressure. The stand-by pump should be arranged to operate automatically in case of failure of the duty pump. The system should have an interlocking arrangement so that only one of the pumps operate at a time.
Wet-Riser-cum-Down-ComerA wet-riser-cum-down-comer system should be provided in the type of buildings indicated in Table 1 of IS 3844 according to the provision mentioned.
Priming of the main pump and terrace pump in case of wet-riser-cum-down, or both the pumps in case of wet-riser installation, should be automatic. This can be achieved either by having flooded suction, or by a priming tank with foot valve arrangement. However, a flooded suction is preferable.
Down-Comer SystemSingle headed landing valve, connected to a 100 mm diameter pipe taken from the terrace pump delivery should be provided at each floor/landing, A hose reel conforming to IS 884 : 1985 and directly tapped from the down-comer pipe should also be provided on each floor/landing.

 

As per ( IS 3844 )

RiserThe position of risers should be located within lobby approach staircase or within, the staircase enclosure when there is no lobby. However, the risers or the landing valves connected
Landing ValveLanding valves should be installed on each floor level and on the roof, if accessible, in such
a way that control line of landing valve is 1 to 1.2 m above the floor level.
Fire HosesIn buildings with basements, the internal hydrants as well as the hose reel installations should be extended to cover the basement area also, over and above sprinkler system, as necessary. .
Fire hoses should be of sufficient length to, carry water from the nearest source of water supply to the most distant point in the area covered by a hydrant, by the normal route of travel. For each internal hydrant ( single headed ), there should be a total length of not less than.30 m of 63 mm conforming to Type A of IS 636 : 1988 or provided in two lengths of not more than 15 m each wire wound with coupling together with branch pipe conforming to IS 2871 : 1983
Such spare hoses also should be in length of not more than 15 m complete with coupling. Hoses and accessories should be kept in hose cabinet painted fire red and constructed preferably of wood with glass front
Hose BoxUnless impracticable by structural considerations, the landing valves should always be housed in hose boxes. Such hose boxes should be made of MS plates of 2 mm minimum thickness with glass front. The size of the box should be adequate to accommodate single/double headed landing valves with 2 or 4 lengths of fire hose each of 15 m length, and one or two branch pipes. The hose reel may or may not be accommodated inside the hose box.
Building fitted with wet-riser/wet-riser-down-comer mains should, have access roads to within 6 m from the boundary line of the building and the nearest wet-riser stack should not be more than 15 m from the boundary line of the building.
Hose ReelsIn addition to wet-riser systems, first aid hose reels should be installed on all floors of buildings above 15 m in height. The hose reel should be directly taken from the wet-riser pipe by means of a 37 mm socket and pipe to which the hose reel is to be attached.
The hose reel should be sited at each floor level, staircase, lobby or mid-landing adjacent to, exits in corridors in such a way that the nozzle of the hose can be taken into every room and within 6 m of any part of a room keeping in view the layout and obstructions. Tbe doors provided for the hose reel recesses should he capable of opening to approximately 180”. when installation is in open areas, the position should be above head height and the nozzle retainer and tbe inlet valve should be at about 900 mm above floor level.
Air ValveTo allow any trapped air in the rising main to escape when water is pressurized into system,air release valve should be incorporated above the highest outlet of each main.
External HydrantFor external hydrants, piping (water main ) should be laid preferably underground, to avoid it getting damaged by moving vehicles, etc. To avoid rusting, underground pipes should be either of cast iron conforming to IS 1536 in which case it should be properly treated with a coat of primary paint with two coats of bitumen paint. The pipes should be properly supported of pedestals – not more than 3 m apart. Underground pipes should be laid 1 m below to avoid damage during road repair, etc, and at road crossings where heavy vehicles are expected to pass, it should pass
Jockey PumpFor bigger buildings or major installations, where chance of such leakage is very considerable, it is desirable to install a small pump ( using a small motor and 200/300 liter/min pump ) with pressure switches for automatic start and stop.
Using Wet-Riser System Pump for Partial Sprinkler SystemIn main high rise buildings, the basement is used for car parking/housing transformers/or storages and other floors may be used as shopping areas departmental stores, etc, the total area used for such purpose being small, in such cases, the same wet-riser pump may be used for feeding the sprinkler system provided that:
a)the total area of the basement to be protected is less than 500 m2.
b) the total area utilized as shops departmental stores is less than 1000 m2.
c)the pump has a capacity of at least 2850 l/min with suitable motor.

 

AS per IS 15301

Foundation of PumpPumps are to be mounted on a concrete foundation having minimum M grade of reinforced concrete as M15..
The thickness of the foundation shall be 50 mm minimum for small pumps up to 900 Liter/min capacity, 75 mm for pumps up to 2280 liter/min capacity and 100 liter/min for bigger pumps up to 4 500 liter/min. For extra ordinary big pumps, the thickness may go up to 150 mm. The size of the foundation shall cover the full length and width of the pump and at least 150 mm on the front and back of the pump and 75 mm on the sides as clearance.
Pump Room LocationNormally, pump rooms shall be located 6 m away from all surrounding buildings and overhead structures
 Where this is not feasible, they may be attached to a building provided a perfect separation wall having 4 hour fire rating is constructed between the pump room and the attached building, the roof of the pump room is of RCC construction atleast 100 mm thick and access to the pump room is from the outside. The pump rooms shall normally have brick/concrete walls and noncombustible roof with adequate lighting, ventilation and drainage arrangements.
Transformer cubicles inside the sub-stations shall be separated from H.T. and L.T. cubicles and from each other by walls of brick/stone/concrete blocks or 355 mm thickness or of RCC of 200 mm thickness with door openings, if any, therein being protected by single fireproof doors having 2-hour fire resistance
Transformers installed outdoors, which are supplying power to fire pump shall also be located at least 6 m away from all surrounding buildings including sub-station or D.G. House, Where this is not feasible, all door and window openings of the building within 6 m of the transformers] shall be protected by single fireproof doors and 6 mm thick wired glasses in steel
framework respectively.

 

Requirement of the Fire Safety for Group A – Residential Buildings – Above 15 m in height  (IS 3844)

Type of Fire Protection RequiredA3- Dormitories, A4- Apartments HousesA5- Hotels
Fire Safety15 Mts To 35 Mts35 Mts To  45 Mts45 Mts To 60 MtsAbove 60 Mts15 Mts To  30 MtsAbove 30 Mts and A6 Hotels (Starred)
Fire ExtinguishersMinimum 2 per floor Depending upon the Area and Travel Distance
Terrace Level Over Head Tank25,000 liters capacity5,000 liters (5,000 liters if basement)10,000 liters capacity25,000 liters capacity20,000 liters capacity20,000 liters capacity
Under Ground Water TankNot Required75,000 liters capacity75,000 liters capacity1,00,000 liters capacity1,50,000 liters capacity2,00,000 liters capacity
Terrace Fire Pump900 LPM at Terrace level TankNot RequiredNot RequiredNot RequiredNot RequiredNot Required
Fire Pump near Under Group Water TankNot Required1 electric pump & 1 Diesel pump of capacity 1620 LPM & Jockey Pump 180 LPM1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM1 electric pump & 1 Diesel pump of capacity 2280LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2850 LPM & Jockey Pump 180 LPM
Hose Reel AssemblyRequiredRequiredRequiredRequiredRequiredRequired
Down Comer SystemRequiredNot RequiredNot RequiredNot RequiredNot RequiredNot Required
Wet Riser SystemNot RequiredRequiredRequiredRequiredRequiredRequired
Yard HydrantNot RequiredNot RequiredRequiredRequiredRequiredRequired
Fire Service InletRequiredRequiredRequiredRequiredRequiredRequired
Manually Operated Fire Alarm Call Point (MCP)RequiredRequiredRequiredRequiredRequiredRequired
Automatic Detection & Alarm SystemNot RequiredNot RequiredNot RequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequired if area of basement exceeds 200 Sq.mtsRequired if area of basement exceeds 200 Sq.mtsRequiredRequiredRequiredRequired

 

Requirements of Fire Safety for Group B – Educational Buildings of above 15 mts in height (IS 3844)

Type of Fire Protection Required B-1 Schools up to Senior Secondary Level 
B-2 All others/training Institutions  (Ground + One Storey)
Fire ExtinguishersMinimum 2 per floor. Depending up on the Area and Travel Distance
Terrace Level Over Head Tank25000 Liters Capacity
Under Ground Water TankNot required
Terrace Fire Pump900 LPM
Fire Pump near Under Ground Water TankNot required
Hose Reel AssemblyRequired
Down Comes SystemRequired
Wet Riser SystemNot required
Yard HydrantNot required
Fire Service InletRequired
Manually  Fire Alarm Call Point (MCP)Required
Automatic Detection and Alarm SystemNot required
Automatic Sprinkler SystemRequired if area of basement exceeds 200 sq.mts

 

Requirement of the Fire Safety for Group C – Institutional Buildings – Above 15 m in height (IS 3844)

Type of Fire Protection RequiredC1- Hospitals,  Sanatoria and Nursing HomeC2 – Custodial Institutions
C3 – Penal and Mental Institutions
Fire Safety (Active Measures)15 Mts not exceeding24 Mts not exceeding15 Mts not exceeding24 Mts not exceeding
24  Mts30 Mts24 Mts30 Mts
Fire ExtinguishersMinimum 2 per floor Depending upon the Area and Travel Distance
Terrace Level Over Head Tank20,000 liters capacity20,000 liters capacity10,000 liters capacity20,000 liters capacity
Under Ground Water Tank1.00,000 liters capacity1,50,000 liters capacity75,000 liters capacity1,00,000 liters capacity
Terrace Fire PumpNot requiredNot RequiredNot RequiredNot Required
Fire Pump near Under Group Water Tank1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM
Hose Reel AssemblyRequiredRequired RequiredRequired
Down Comer SystemNot RequiredNot RequiredNot RequiredNot Required
Wet Riser SystemRequiredRequiredRequiredRequired
Yard HydrantRequiredRequiredRequiredRequired
Fire Service InletRequiredRequiredRequiredRequired
Manually Operated Fire Alarm Call Point (MCP)RequiredRequiredRequiredRequired
Automatic Detection & Alarm SystemRequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequiredRequired

 

Requirement of the Fire Safety for Group D – Assembly Buildings Above 15 m in height (IS 3844)

Type of Fire Protection RequiredD1 – Theater over  1000 persons, D2 up to 1000 persons  D3 – Permanent Stage over 300 personsD6 – Not exceeding 30 mtrsD7 – Elevated or underground for assembly not  covered D1-D6
D4 – up to 300 persons, D5 all others
Fire Safety15 Mts To 24 Mts24 Mts To 30 Mts15 Mts not exceeding24 Mts not exceeding
Fire ExtinguishersMinimum 2 per floor Depending upon the Area and Travel Distance
Terrace Level Over Head Tank10,000 liters capacity20,000 liters capacity20,000 liters capacity20,000 liters capacity
Under Ground Water Tank75,000 liters capacity1,00,000 liters capacity1,00,000 liters capacity1,00,000 liters capacity
D1-D5, 2,00,000 liters for D6 Multiplex
Terrace Fire PumpNot requiredNot RequiredNot RequiredNot Required
Fire Pump near Under Group Water Tank1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2850 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2850 LPM & Jockey Pump 180 LPM
Hose Reel AssemblyRequiredRequiredRequiredRequired
Down Comer SystemNot RequiredNot RequiredNot RequiredNot Required
Wet Riser SystemRequiredRequiredRequiredRequired
Yard HydrantRequiredRequiredRequiredRequired
Fire Service InletRequiredRequiredRequiredRequired
Manually Operated Fire Alarm Call Point (MCP)RequiredRequiredRequiredRequired
Automatic Detection & Alarm SystemRequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequiredRequired

 

Requirement of the Fire Safety for Group E – Business Buildings  Above 15 m in height (IS 3844)

Type of Fire Protection RequiredE1  offices, banks, professional establishments, like offices of architects, engineers, doctors, lawyers and police stations, E2 – Laboratories research establishments, libraries and test houses.  E3 – Computer installations, E4 – Telephone Exchanges,  E5
Fire Safety15 Mts To 24 Mts24 Mts To 30 MtsAbove 30 mt
Fire ExtinguishersMinimum 2 per floor Depending upon the Area and Travel DistanceMinimum 2 per floor Depending upon the Area and Travel DistanceMinimum 2 per floor Depending upon the Area and Travel Distance
Terrace Level Over Head Tank10,000 liters capacity20,000 liters capacity20,000 liters capacity
Under Ground Water Tank75,000 liters capacity1,00,000 liters capacity2,00,000 liters capacity
Terrace Fire PumpNot requiredNot RequiredNot Required
Fire Pump near Under Group Water Tank1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2850 LPM & Jockey Pump 180 LPM
Hose Reel AssemblyRequiredRequired Required
Down Comer SystemNot RequiredNot RequiredNot Required
Wet Riser SystemRequiredRequiredRequired
Yard HydrantRequiredRequiredRequired
Fire Service InletRequiredRequiredRequired
Manually Operated Fire Alarm Call Point (MCP)RequiredRequiredRequired
Automatic Detection & Alarm SystemRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequired

 

Requirement of the Fire Safety for Group F Mercantile Building  Above 15 m in height (IS 3844)

Type of Fire Protection RequiredF1  – Shops, Stores up to 500 Sq.m,F3 – Underground shopping centre and  Storage
F2 – Shops, Stores more than 500 Sq. mtrs.
Fire Safety (Active Measures)15 Mts To 24 Mts24 Mts To 30 Mts
Fire ExtinguishersMinimum 2 per floor Depending upon the Area and Travel Distance
Terrace Level Over Head Tank10,000 liters capacity10,000 liters capacity10,000 liters capacity
Under Ground Water Tank1,00,000 liters capacity1,50,000 liters capacity1,50,000 liters capacity
Terrace Fire PumpNot requiredNot RequiredNot Required
Fire Pump near Under Group Water Tank1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM2 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM
Hose Reel AssemblyRequiredRequiredRequired
Down Comer SystemNot RequiredNot RequiredNot Required
Wet Riser SystemRequiredRequiredRequired
Yard HydrantRequiredRequiredRequired
Fire Service InletRequiredRequiredRequired
Manually Fire Call Point (MCP)RequiredRequiredRequired
Automatic Detection & Alarm SystemRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequired

 

Requirement of the Fire Safety for Group G Industrial Buildings  Above 15 m in height not to be permitted 18 Mts in height (IS 3844)

Type of Fire ProtectionG1  – Low Hazard IndustriesG2 – Moderate Hazard Industries
BUILT UP AREA
Fire SafetyUp to 100 Sq.mtMore than  100 Sq.mt. & up to 500 Sq.mtMore than 500 Sq.mtrsUp to 100Sq.mtrsMore than  100Sq.mtrs and up to 500 Sq.mtrsMore than  500Sq.mtrs and up to 1000 Sq.mtrsUp to 1000 Sq.mt
Fire ExtinguishersMinimum 2 per floor Depending upon the Area and Travel Distance
Terrace Level Over Head Tank5000 liters in case of basement area exceeds 200m25000 liters add 5000 liters if the provision of sprinkler in basement10,000 liters capacity10,000 Liters capacity10,000 Liters capacity20,000 Liters capacity20,000 Liters capacity
Under Ground Water TankNot requiredNot required1,00,000 litersNot requiredNot required75,000 Liters capacity1,00,000 Liters capacity
Terrace Fire Pump450 LPM450 LPM450 LPM900 LPM900 LPM900 LPM900 LPM
Fire Pump near Under Group Water TankNot requiredNot required1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPMNot requiredNot required1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM1 electric pump & 1 Diesel pump of capacity 2280 LPM & Jockey Pump 180 LPM
Hose Reel AssemblyNot requiredRequiredRequiredRequiredRequiredRequiredRequired
Down Comer SystemNot requiredRequiredRequiredNot requiredNot requiredRequiredRequired
Wet Riser SystemNot requiredNot requiredRequiredNot RequiredNot RequiredRequiredRequired
Yard HydrantNot requiredNot requiredRequiredNot RequiredNot RequiredRequiredRequired
Fire Service InletNot requiredNot requiredRequiredNot RequiredNot RequiredRequiredRequired
Manually Operated Fire Alarm Call Point (MCP)Not requiredNot requiredNot RequiredNot RequiredNot RequiredRequiredRequired
Automatic Detection & Alarm SystemNot requiredNot requiredRequiredNot RequiredNot RequiredRequiredRequired
Automatic Sprinkler SystemRequired (if there is basement)Required (if there is basement)RequiredRequiredRequiredRequiredRequired