PCV Cable-Current Rating
Flexible PVC Insulated Cable
PVC- Insulated 1 core unsheathed / Sheathed flexible cord with copper conductor 1.1KV ( As per IS:694 – 1990 ) | |||||||||
Nominal Conductor Area (Sq.mm) | UN SHEATHED | SHEATHED | Maximum Conductor Resistance at 20°C (ohm/km) | Current Carrying Capacity (Amp) | |||||
Nominal Thickness of Insulation (mm) | Maximum overall Diameter (mm) | Approx. Weight (kg/100m) | Nominal Thickness of Insulation (mm) | Nominal Thickness of Sheath (mm) | Maximum Overall Diameter (mm) | Approx. Weight (kg/100m) | |||
1cX0.5 | 0.6 | 2.3 | 0.9 | 0.6 | 0.9 | 4.5 | 2.6 | 39 | 4 |
1cX0.75 | 0.6 | 2.5 | 1.2 | 0.6 | 0.9 | 4.7 | 3 | 26 | 7 |
1cX1 | 0.6 | 2.7 | 1.5 | 0.6 | 0.9 | 4.9 | 3.4 | 19.5 | 11 |
1cX1.5 | 0.6 | 3 | 2 | 0.6 | 0.9 | 5.4 | 4.3 | 13.3 | 15 |
1cX2.5 | 0.7 | 3.7 | 3.2 | 0.7 | 1 | 6.2 | 6 | 7.98 | 19 |
1cX4 | 0.8 | 4.4 | 4.9 | 0.8 | 1 | 7 | 8.2 | 4.95 | 26 |
1cX6 | 0.8 | 5 | 7 | 0.8 | 1 | 7.4 | 10.3 | 3.3 | 35 |
1cX10 | 1 | 7 | 11.9 | 1 | 1 | 7.7 | 13 | 1.91 | 46 |
1cX16 | 1 | 9 | 20.1 | 1 | 1 | 9.8 | 21.8 | 1.21 | 62 |
1cX25 | 1.2 | 10 | 27.4 | 1.2 | 1.1 | 12 | 32.1 | 0.78 | 80 |
1cX35 | 1.2 | 11.4 | 36.7 | 1.2 | 1.1 | 13 | 42.7 | 0.554 | 102 |
1cX50 | 1.4 | 13.5 | 52.5 | 1.4 | 1.2 | 15 | 59.7 | 0.386 | 138 |
1cX70 | 1.4 | 16 | 72.3 | 1.4 | 1.2 | 17.8 | 80.6 | 0.272 | 214 |
1cX95 | 1.6 | 18 | 96.1 | 1.6 | 1.4 | 20.7 | 108.1 | 0.206 | 254 |
1cX120 | 1.6 | 20.5 | 120.3 | 1.6 | 1.4 | 22.2 | 132.5 | 0.161 | 300 |
PVC- Insulated and PVC – Sheathed 2 core flexible cord with copper conductor 1.1KV ( As per IS:694 – 1990 ) | |||||||||
Nominal Conductor Area (Sq.mm) | Nominal Thickness of Insulation (mm) | Nominal Thickness of Sheath (mm) | 2 CORE CIRCULAR | 2 CORE FLAT | Maximum Conductor Resistance at 20°C (ohm/km) | Current Carrying Capacity (Amp) | |||
Maximum overall Diameter (mm) | Approx. Weight (kg/100m) | Maximum overall Diameter (mm) | Approx. Weight (kg/100m) | ||||||
2cX0.5 | 0.6 | 0.9 | 7.2 | 5.5 | 4.9×7.2 | 4.7 | 39 | 4 | |
2cX0.75 | 0.6 | 0.9 | 7.8 | 6.5 | 5.2×7.8 | 5.5 | 26 | 7 | |
2cX1 | 0.6 | 0.9 | 8 | 7.5 | 5.4×8.0 | 6.3 | 19.5 | 11 | |
2cX1.5 | 0.6 | 0.9 | 8.6 | 9.2 | 5.6×8.6 | 8 | 13.3 | 15 | |
2cX2.5 | 0.7 | 1 | 10.5 | 13.5 | 6.6×10.5 | 11.2 | 7.98 | 19 | |
2cX4 | 0.8 | 1 | 12 | 19 | 7.2×12.0 | 15.8 | 4.95 | 26 | |
PVC- Insulated and PVC – Sheathed 3 core flexible cord with copper conductor 1.1KV ( As per IS:694 – 1990 ) | |||||||||
Nominal Conductor Area (Sq.mm) | Nominal Thickness of Insulation (mm) | Nominal Thickness of Sheath (mm) | 3 CORE CIRCULAR | 3 CORE FLAT | Maximum Conductor Resistance at 20°C (ohm/km) | Current Carrying Capacity (Amp) | |||
Maximum overall Diameter (mm) | Approx. Weight (kg/100m) | Maximum overall Diameter (mm) | Approx. Weight (kg/100m) | ||||||
3cX0.5 | 0.6 | 0.9 | 7.6 | 6.4 | 0.9 | 5.1 | 39 | 4 | |
3cX0.75 | 0.6 | 0.9 | 8.2 | 7.6 | 0.9 | 6.1 | 26 | 7 | |
3cX1 | 0.6 | 0.9 | 9.2 | 10.9 | 0.9 | 7.1 | 19.5 | 11 | |
3cX1.5 | 0.6 | 0.9 | 9.2 | 10.9 | 0.9 | 8.7 | 13.3 | 15 | |
3cX2.5 | 0.7 | 1 | 11 | 16.2 | 1 | 13 | 7.98 | 19 | |
3cX4 | 0.8 | 1 | 12.5 | 23.7 | 1 | 18.6 | 4.95 | 26 |
PVC Insulated Armored & Unarmored Cables:
1.1 KV SINGLE CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | UN-ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminum | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
1cX4 | 8 | — | — | — | 39 | 38 | 35 | 0.304 | 0.460 |
1cX 6 | 9 | 39 | 37 | 35 | 49 | 48 | 44 | 0.456 | 0.690 |
1cX10 | 10 | 51 | 51 | 47 | 65 | 64 | 60 | 0.760 | 1.150 |
1cX16 | 11 | 66 | 65 | 64 | 85 | 83 | 82 | 1.220 | 1.84 |
1cX25 | 13 | 86 | 84 | 84 | 110 | 110 | 110 | 1.900 | 2.88 |
1cX 35 | 14 | 100 | 100 | 105 | 130 | 125 | 130 | 2.660 | 4.03 |
1cX50 | 16 | 120 | 115 | 130 | 155 | 150 | 165 | 3.800 | 5.75 |
1cX70 | 17 | 140 | 135 | 155 | 190 | 175 | 205 | 5.320 | 8.05 |
1cX 95 | 19 | 175 | 155 | 190 | 220 | 200 | 245 | 7.220 | 10.90 |
1cX120 | 21 | 195 | 170 | 220 | 250 | 220 | 280 | 9.120 | 13.80 |
1cX150 | 23 | 220 | 190 | 250 | 280 | 245 | 320 | 11.40 | 17.30 |
1cX185 | 25 | 240 | 210 | 290 | 305 | 260 | 370 | 14.10 | 21.30 |
1cX240 | 28 | 270 | 225 | 335 | 345 | 285 | 425 | 18.20 | 27.30 |
1cX300 | 30 | 295 | 245 | 380 | 375 | 310 | 475 | 22.80 | 34.50 |
1cX400 | 35 | 325 | 275 | 435 | 400 | 335 | 550 | 30.40 | 46.00 |
1cX 500 | 38 | 345 | 295 | 480 | 425 | 355 | 590 | 38.00 | 57.50 |
1cX 630 | 43 | 390 | 320 | 550 | 470 | 375 | 660 | 47.90 | 72.50 |
1cX800 | 48 | 450 | 380 | 610 | 530 | 425 | 725 | 60.80 | 92.00 |
1cX1000 | 52 | 500 | 415 | 680 | 590 | 740 | 870 | 76.00 | 115.00 |
1.1 KV SINGLE CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
1cX4 | 11 | 31 | 30 | 27 | 39 | 38 | 35 | 0.304 | 0.460 |
1cX 6 | 12 | 39 | 37 | 35 | 49 | 48 | 44 | 0.456 | 0.690 |
1cX10 | 13 | 51 | 51 | 47 | 65 | 64 | 60 | 0.760 | 1.150 |
1cX16 | 14 | 66 | 65 | 64 | 85 | 83 | 82 | 1.220 | 1.840 |
1cX25 | 15 | 86 | 84 | 84 | 110 | 110 | 110 | 1.900 | 2.880 |
1cX 35 | 16 | 100 | 100 | 105 | 130 | 125 | 130 | 2.660 | 4.030 |
1cX50 | 18 | 120 | 115 | 130 | 155 | 150 | 165 | 3.800 | 5.750 |
1cX70 | 20 | 140 | 135 | 155 | 190 | 175 | 205 | 5.320 | 8.050 |
1cX 95 | 22 | 175 | 155 | 190 | 220 | 200 | 245 | 7.220 | 10.90 |
1cX120 | 24 | 195 | 170 | 220 | 250 | 220 | 280 | 9.120 | 13.80 |
1cX150 | 26 | 220 | 190 | 250 | 280 | 245 | 320 | 11.400 | 17.30 |
1cX185 | 29 | 240 | 210 | 290 | 305 | 260 | 370 | 14.100 | 21.30 |
1cX240 | 32 | 270 | 225 | 335 | 345 | 285 | 425 | 18.200 | 27.60 |
1cX300 | 33 | 295 | 245 | 380 | 375 | 310 | 475 | 22.800 | 34.50 |
1cX400 | 39 | 325 | 275 | 435 | 400 | 335 | 550 | 30.400 | 46.00 |
1cX 500 | 42 | 345 | 295 | 480 | 425 | 355 | 590 | 38.000 | 57.50 |
1cX 630 | 48 | 390 | 320 | 550 | 470 | 375 | 660 | 47.880 | 72.50 |
1cX800 | 52 | 450 | 380 | 610 | 530 | 423 | 725 | 60.800 | 92.00 |
1cX1000 | 59 | 500 | 414 | 680 | 590 | 471 | 870 | 76.000 | 115.00 |
1.1 KV Two CORE AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | UN-ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
2cX4 | 14 | 32 | 27 | 27 | 41 | 35 | 35 | 0.304 | 0.460 |
2cX 6 | 17 | 40 | 34 | 35 | 50 | 44 | 45 | 0.456 | 0.690 |
2cX10 | 18 | 55 | 45 | 47 | 70 | 58 | 60 | 0.760 | 1.150 |
2cX16 | 17 | 70 | 58 | 59 | 90 | 75 | 78 | 1.220 | 1.840 |
2cX25 | 19 | 90 | 76 | 78 | 115 | 97 | 105 | 1.900 | 2.880 |
2cX35 | 21 | 110 | 92 | 99 | 140 | 120 | 125 | 2.660 | 4.030 |
2cX50 | 24 | 135 | 115 | 125 | 165 | 145 | 155 | 3.800 | 5.750 |
2cX70 | 26 | 160 | 140 | 150 | 205 | 180 | 195 | 5.320 | 8.050 |
2cX95 | 30 | 190 | 170 | 185 | 240 | 215 | 230 | 7.220 | 10.90 |
2cX120 | 32 | 210 | 190 | 210 | 275 | 235 | 265 | 9.120 | 13.80 |
2cX150 | 34 | 240 | 210 | 240 | 310 | 270 | 305 | 11.40 | 17.300 |
2cX185 | 38 | 275 | 240 | 275 | 350 | 300 | 350 | 14.10 | 21.280 |
2cX240 | 42 | 320 | 275 | 325 | 405 | 345 | 410 | 18.20 | 27.600 |
2cX300 | 46 | 355 | 305 | 365 | 450 | 385 | 465 | 22.80 | 34.500 |
2cX400 | 52 | 385 | 345 | 420 | 490 | 485 | 530 | 30.40 | 46.000 |
2cX500 | 54 | 425 | 380 | 475 | 540 | 460 | 605 | 38.00 | 57.500 |
2cX630 | 65 | 465 | 415 | 540 | 640 | 550 | 785 | 47.90 | 72.550 |
1.1 KV Two CORE AL/COPPER COND., PVC INSULATEDCABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
2cX4 | 18 | 32 | 27 | 27 | 41 | 35 | 35 | 0.304 | 0.460 |
2cX 6 | 19 | 40 | 34 | 35 | 50 | 44 | 45 | 0.456 | 0.690 |
2cX10 | 20 | 55 | 45 | 47 | 70 | 58 | 60 | 0.760 | 1.150 |
2cX16 | 20 | 70 | 58 | 59 | 90 | 75 | 78 | 1.220 | 1.840 |
2cX25 | 22 | 90 | 76 | 78 | 115 | 97 | 105 | 1.90 | 2.880 |
2cX35 | 23 | 110 | 92 | 99 | 140 | 120 | 125 | 2.66 | 4.030 |
2cX50 | 26 | 135 | 115 | 125 | 165 | 145 | 155 | 3.80 | 5.750 |
2cX70 | 29 | 160 | 140 | 150 | 205 | 180 | 195 | 5.32 | 8.050 |
2cX95 | 33 | 190 | 170 | 185 | 240 | 215 | 230 | 7.22 | 10.90 |
2cX120 | 35 | 210 | 190 | 210 | 275 | 235 | 265 | 9.12 | 13.80 |
2cX150 | 37 | 240 | 210 | 240 | 310 | 270 | 305 | 11.40 | 17.30 |
2cX185 | 41 | 275 | 240 | 275 | 350 | 300 | 350 | 14.10 | 21.30 |
2cX240 | 47 | 320 | 275 | 325 | 405 | 345 | 410 | 18.20 | 27.60 |
2cX300 | 50 | 355 | 305 | 365 | 450 | 385 | 465 | 22.80 | 34.50 |
2cX400 | 58 | 385 | 345 | 420 | 490 | 485 | 530 | 30.40 | 46.00 |
2cX500 | 64 | 425 | 380 | 475 | 540 | 460 | 605 | 38.00 | 57.50 |
2cX630 | 72 | 465 | 415 | 540 | 640 | 550 | 785 | 47.90 | 72.50 |
1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | UN-ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
3cX 4 | 16 | 28 | 23 | 23 | 36 | 30 | 30 | 0.304 | 0.460 |
3cX 6 | 18 | 35 | 30 | 30 | 45 | 38 | 39 | 0.456 | 0.690 |
3cX 10 | 19 | 46 | 39 | 40 | 60 | 50 | 52 | 0.760 | 1.150 |
3cX 16 | 19 | 60 | 50 | 51 | 77 | 64 | 66 | 1.220 | 1.840 |
3cX 25 | 22 | 76 | 63 | 70 | 99 | 81 | 90 | 1.900 | 2.880 |
3cX 35 | 24 | 92 | 77 | 86 | 120 | 99 | 110 | 2.660 | 4.030 |
3cX 50 | 27 | 110 | 95 | 105 | 145 | 125 | 135 | 3.800 | 5.750 |
3cX 70 | 30 | 135 | 115 | 130 | 175 | 150 | 165 | 5.320 | 8.050 |
3cX 95 | 34 | 165 | 140 | 155 | 210 | 175 | 200 | 7.220 | 10.900 |
3cX 120 | 37 | 185 | 155 | 180 | 240 | 195 | 230 | 9.120 | 13.800 |
3cX 150 | 40 | 210 | 175 | 205 | 270 | 225 | 265 | 11.40 | 17.300 |
3cX 185 | 44 | 235 | 200 | 240 | 300 | 255 | 305 | 14.10 | 21.300 |
3cX 240 | 50 | 275 | 235 | 280 | 345 | 295 | 355 | 18.20 | 27.600 |
3cX 300 | 55 | 305 | 260 | 315 | 385 | 335 | 400 | 22.80 | 34.500 |
3cX 400 | 62 | 335 | 290 | 375 | 425 | 360 | 435 | 30.40 | 46.000 |
3cX 500 | 69 | 370 | 320 | 425 | 470 | 390 | 520 | 38.00 | 57.500 |
3cX 630 | 77 | 405 | 350 | 480 | 555 | 470 | 675 | 47.90 | 72.500 |
1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
3cX 4 | 18 | 28 | 23 | 23 | 36 | 30 | 30 | 0.304 | 0.460 |
3cX 6 | 19 | 35 | 30 | 30 | 45 | 38 | 39 | 0.456 | 0.690 |
3cX 10 | 21 | 46 | 39 | 40 | 60 | 50 | 52 | 0.760 | 1.150 |
3cX 16 | 21 | 60 | 50 | 51 | 77 | 64 | 66 | 1.220 | 1.840 |
3cX 25 | 23 | 76 | 63 | 70 | 99 | 81 | 90 | 1.900 | 2.880 |
3cX 35 | 26 | 92 | 77 | 86 | 120 | 99 | 110 | 2.660 | 4.030 |
3cX 50 | 29 | 110 | 95 | 105 | 145 | 125 | 135 | 3.800 | 5.750 |
3cX 70 | 33 | 135 | 115 | 130 | 175 | 150 | 165 | 5.320 | 8.050 |
3cX 95 | 37 | 165 | 140 | 155 | 210 | 175 | 200 | 7.220 | 10.900 |
3cX 120 | 39 | 185 | 155 | 180 | 240 | 195 | 230 | 9.120 | 13.800 |
3cX 150 | 43 | 210 | 175 | 205 | 270 | 225 | 265 | 11.400 | 17.300 |
3cX 185 | 49 | 235 | 200 | 240 | 300 | 255 | 305 | 14.100 | 21.300 |
3cX 240 | 54 | 275 | 235 | 280 | 345 | 295 | 355 | 18.200 | 27.600 |
3cX 300 | 59 | 305 | 260 | 315 | 385 | 335 | 400 | 22.800 | 34.500 |
3cX 400 | 68 | 335 | 290 | 375 | 425 | 360 | 435 | 30.400 | 46.000 |
3cX 500 | 75 | 370 | 320 | 425 | 470 | 390 | 520 | 38.000 | 57.500 |
3cX 630 | 84 | 405 | 350 | 480 | 555 | 470 | 675 | 47.900 | 72.500 |
1.1 KV Three & Half CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | UN-ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
3.5X25 | 24 | 76 | 63 | 70 | 99 | 81 | 90 | 1.90 | 2.88 |
3.5X35 | 26 | 92 | 77 | 86 | 120 | 99 | 110 | 2.66 | 4.03 |
3.5X50 | 29 | 110 | 95 | 105 | 145 | 125 | 135 | 3.80 | 5.75 |
3.5X70 | 32 | 135 | 115 | 130 | 175 | 150 | 165 | 5.32 | 8.05 |
3.5X95 | 36 | 165 | 140 | 155 | 210 | 175 | 200 | 7.22 | 10.90 |
3.5X120 | 40 | 185 | 155 | 180 | 240 | 195 | 230 | 9.12 | 13.80 |
3.5X150 | 44 | 210 | 175 | 205 | 270 | 225 | 265 | 11.40 | 17.30 |
3.5X185 | 48 | 235 | 200 | 240 | 300 | 255 | 305 | 14.10 | 21.30 |
3.5X240 | 54 | 275 | 235 | 280 | 345 | 295 | 355 | 18.20 | 27.60 |
3.5X300 | 62 | 305 | 260 | 315 | 385 | 335 | 400 | 22.80 | 34.50 |
3.5X400 | 68 | 335 | 290 | 375 | 425 | 360 | 435 | 30.40 | 46.00 |
3.5X500 | 77 | 370 | 320 | 425 | 470 | 390 | 520 | 38.00 | 57.50 |
3.5X630 | 87 | 405 | 350 | 480 | 555 | 470 | 675 | 47.90 | 72.50 |
1.1 KV Three & Half CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
3.5X25 | 26 | 76 | 63 | 70 | 99 | 81 | 90 | 1.90 | 2.88 |
3.5X35 | 28 | 92 | 77 | 86 | 120 | 99 | 110 | 2.66 | 4.03 |
3.5X50 | 31 | 110 | 95 | 105 | 145 | 125 | 135 | 3.80 | 5.75 |
3.5X70 | 36 | 135 | 115 | 130 | 175 | 150 | 165 | 5.32 | 8.05 |
3.5X95 | 39 | 165 | 140 | 155 | 210 | 175 | 200 | 7.22 | 10.90 |
3.5X120 | 43 | 185 | 155 | 180 | 240 | 195 | 230 | 9.12 | 13.80 |
3.5X150 | 47 | 210 | 175 | 205 | 270 | 225 | 265 | 11.40 | 17.30 |
3.5X185 | 53 | 235 | 200 | 240 | 300 | 255 | 305 | 14.10 | 21.30 |
3.5X240 | 58 | 275 | 235 | 280 | 345 | 295 | 355 | 18.20 | 27.60 |
3.5X300 | 65 | 305 | 260 | 315 | 385 | 335 | 400 | 22.80 | 34.50 |
3.5X400 | 75 | 335 | 290 | 375 | 425 | 360 | 435 | 30.40 | 46.00 |
3.5X500 | 84 | 370 | 320 | 425 | 470 | 390 | 520 | 38.00 | 57.50 |
3.5X630 | 92 | 405 | 350 | 480 | 555 | 470 | 675 | 47.90 | 72.50 |
1.1 KV Four CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | UN-ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
4cX4 | 16 | 28 | 23 | 23 | 36 | 30 | 30 | 0.304 | 0.460 |
4cX 6 | 18 | 35 | 30 | 30 | 45 | 38 | 39 | 0.456 | 0.690 |
4cX 10 | 20 | 46 | 39 | 40 | 60 | 50 | 52 | 0.760 | 1.150 |
4cX16 | 23 | 60 | 50 | 51 | 77 | 64 | 66 | 1.220 | 1.840 |
4cX 25 | 26 | 76 | 63 | 70 | 99 | 81 | 90 | 1.900 | 2.880 |
4cX35 | 30 | 92 | 77 | 86 | 120 | 99 | 110 | 2.660 | 4.030 |
4cX 50 | 34 | 110 | 95 | 105 | 145 | 125 | 135 | 3.800 | 5.750 |
4cX70 | 38 | 135 | 115 | 130 | 175 | 150 | 165 | 5.320 | 8.050 |
4cX 95 | 43 | 165 | 140 | 155 | 210 | 175 | 200 | 7.220 | 10.900 |
4cX 120 | 46 | 185 | 155 | 180 | 240 | 195 | 230 | 9.120 | 13.800 |
4cX 150 | 51 | 210 | 175 | 205 | 270 | 225 | 265 | 11.400 | 17.300 |
4cX 185 | 55 | 235 | 200 | 240 | 300 | 255 | 305 | 14.100 | 21.300 |
4cX 240 | 60 | 275 | 235 | 280 | 345 | 295 | 355 | 18.200 | 27.600 |
4cX 300 | 66 | 305 | 260 | 315 | 385 | 335 | 400 | 22.800 | 34.500 |
4cX 400 | 73 | 335 | 290 | 375 | 425 | 360 | 435 | 30.400 | 46.000 |
4cX 500 | 82 | 370 | 320 | 425 | 470 | 390 | 520 | 38.000 | 57.500 |
4cX 630 | 92 | 405 | 350 | 480 | 555 | 470 | 675 | 47.900 | 72.500 |
1.1 KV Four CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) | |||||||||
Cross-sectional area (Sq MM) | ARMOURED CABLE | ||||||||
Overall Diameter (mm) | Normal Current Rating in Amps | Short Circuit Current Rating for 1Sec.duration in K. Amps | |||||||
Aluminums Conductor | Copper Conductor | Aluminums | Copper | ||||||
Ground | Duct | Air | Ground | Duct | Air | ||||
4cX4 | 18 | 28 | 23 | 23 | 36 | 30 | 30 | 0.304 | 0.460 |
4cX 6 | 21 | 35 | 30 | 30 | 45 | 38 | 39 | 0.456 | 0.690 |
4cX 10 | 22 | 46 | 39 | 40 | 60 | 50 | 52 | 0.760 | 1.150 |
4cX16 | 23 | 60 | 50 | 51 | 77 | 64 | 66 | 1.220 | 1.840 |
4cX 25 | 27 | 76 | 63 | 70 | 99 | 81 | 90 | 1.900 | 2.880 |
4cX35 | 30 | 92 | 77 | 86 | 120 | 99 | 110 | 2.660 | 4.030 |
4cX 50 | 34 | 110 | 95 | 105 | 145 | 125 | 135 | 3.800 | 5.750 |
4cX70 | 37 | 135 | 115 | 130 | 175 | 150 | 165 | 5.320 | 8.050 |
4cX 95 | 42 | 165 | 140 | 155 | 210 | 175 | 200 | 7.220 | 10.900 |
4cX 120 | 47 | 185 | 155 | 180 | 240 | 195 | 230 | 9.120 | 13.800 |
4cX 150 | 51 | 210 | 175 | 205 | 270 | 225 | 265 | 11.40 | 17.300 |
4cX 185 | 56 | 235 | 200 | 240 | 300 | 255 | 305 | 14.10 | 21.300 |
4cX 240 | 62 | 275 | 235 | 280 | 345 | 295 | 355 | 18.20 | 27.600 |
4cX 300 | 70 | 305 | 260 | 315 | 385 | 335 | 400 | 22.80 | 34.500 |
4cX 400 | 76 | 0.70 | 335 | 290 | 375 | 425 | 360 | 435 | 30.40 |
4cX 500 | 86 | 0.70 | 370 | 320 | 425 | 470 | 390 | 520 | 38.00 |
4cX 630 | 96 | 0.70 | 405 | 350 | 480 | 555 | 470 | 675 | 47.90 |