Minimum Acceptable Specification of C.T & P.T for Metering
Min. Acceptable Specification of Current Transformer for Metering:
Sr. No | Particulars | 11 kV | 33 kV | 132 kV | 220 kV |
1 | Highest System Voltage (kV rms) | 12 | 36 | 145 | 245 |
2 | CT ratio. | 2000-1000/1-1 | 800-400/1-1 | 400/1-1 | 800/1-1 |
1600-800/1-1 | 600-300/1-1 | ||||
1200-600/1-1 | 400-200/1-1 | ||||
800-400/1-1 | 300-150/1-1 | ||||
600-300/1-1 | 100-50/1-1 | ||||
400-200/1-1 | |||||
300-150/1-1 | |||||
150-75/1-1 | |||||
3 | Number of metering cores | Two Nos | Two Nos | Two Nos | Two Nos |
4 | Rated continuous thermal current. | 120% of rated primary current | 120% of rated primary current | 120% of rated primary current | 120% of rated primary current |
5 | Rated short time thermal current of primary for 1 sec. (kA) | 25 | 25 | 31.5 | 40 |
6 | CT characteristics :a) Rated primary current (Amps.) | 2000-1000 | 800-400 | 400 | 800 |
1600-800 | 600-300 | ||||
1200-600 | 400-200 | ||||
800-400 | 300-150 | ||||
600-300 | 100-50 | ||||
400-200 | |||||
300-150 | |||||
150-75 | |||||
(b) Rated Secondary current (Amps.) | 1 | 1 | 1 | 1 | |
(c) Class of accuracy. | 0.2 | 0.2 | 0.2 | 0.2 | |
(d) Max. instrument security factor | 5 | 5 | 5 | 5 | |
(e) Rated burden (VA). | 30 | 30 | 30 | 40 | |
7 | IS to which CT conforms. | ||||
8 | IS to which insulating oil conforms. |
Min. Acceptable Specification of Voltage Transformer for Metering:
Sr. No | Particulars | 245 kV CVTs | 145 kV CVTs |
1 | Highest SystemVoltage (kV) | 245 kV | 145 kV |
2 | Rated Capacitance (pF) | 4400 pf with tolerance + 10% and – 5% | |
3 | For low voltage terminal over entire carrier frequency range. | ||
(a) Stray capacitance | Shall not exceed 200 pf | ||
(b) Stray conductance | Shall not exceed 20 us | ||
4 | (a) High frequency capacitance for entirecarrier frequency range | within 80% to 150% of rated capacitance | |
(b) Equivalent series resistance over the entire frequency range. | less than 40 Ohms | ||
5 | No. of secondary windings for potential device. | Two | Two |
6 | Transformation ratio: | ||
(i) Winding –I | 20 kV- \/3/110 -\/3V | ||
(ii) Winding –II | 20 kV- \/3/110 -\/3V | ||
7 | Rated secondary burden | ||
(i)Winding –I (VA) | 50 VA | 50 VA | |
(ii) Winding –II (VA) | 50 VA | 50 VA | |
8 | Accuracy Class : | ||
(i)Winding –I (VA) | 0.2 for metering | ||
(ii) Winding –II (VA) | 0.2 for metering | ||
9 | Voltage factor for winding – IVoltage factor for winding – II | 1.2 Cont. & 1.5 for 30 secs.1.2 Cont. & 1.5 for 30 secs. | |
10 | IS to which CVTs conform. | IS 3156 with latest amendment | |
11 | IS to which Insulating Oil conform. | IS 335 with latest amendment | |
Minimum Acceptable Specification of Single Phase PT for Metering:
Sr.No | Particulars | 33 kV | 11 kV |
1 | Highest System Voltage (kV rms) | 36 | 12 |
2 | Transformation ratio. | 33kV/ V3/ 110/ V3 | 11 kV/110 V |
3 | Number of windings. | Two | Two |
4 | Rated output/ burden (VA) per winding /phase. | 50 | 50 |
5 | Accuracy class. (At 10 to 100% of VA burden) | 0.2 | 0.2 |
6 | Rated voltage factor and duration. | 1.2 continuous & 1.5 for 30 secs. | |
7 | IS to which PT conforms. | 3156 with latest amendment |