Internal Electrical Work -Abstract of CPWD

 

Circuits:

TopicAbstracts
Lighting CircuitPer Circuit Not more than 10 Points of Lighting or Total 800Watt which is less
Power CircuitFor Residential Per Circuit Less than 2 No of 5A/15A Plug Socket
Power CircuitFor Non Residential Per Circuit Less than 1 No of 5A/15A Plug Socket
Plug SocketIn Residential wiring ,wiring of Socket outlet shall be done by copper Cable only
Min Size of WireFor Lighting Circuit Smallest size of conductor shall be 1.5 Sq.mm
Min Size of WireFor Power Circuit Smallest size of conductor shall be 4 Sq.mm

Plug Socket

Plug Socket5A/6A or 15A/16A Socket shall be installed at following heights:                                                                   =For Non Residential building 23cm above  floor

=For Kitchen 23cm above  Platform. 

=For Bathroom not Socket is provided in bathroom MCB/IC will be 2.1 mt from fixed appliance and at least 1 mt away from Shower

Switch Board /  D.B

Operating RodOperating Rod/Handle of Distribution Board at the height of min 2mt
D.B ClearanceClear Distance in front of Switch Board/D.B shall be min 1 mt.
D.B ClearanceIf there may be bare connection at back of Switch Board than space behind S/W shall be either less than 20cm or more than 75cm
D.B ClearanceNo fuse Body shall be mounted within 2.5 com edge of D.B or Panel
D.B ClearanceClearance between 2.5 cm is maintained between opposite polarity
Switch BoxSwitch Box or Regular Box shall be mounted normally 1.25 mt from floor level.

Fan Hook

Fan HookFor Fan Hook in concrete roof 12mm dia MS Rod in ‘U’ Shape, horizontally Leg at Top at least 19 cm on either side.

Connection between adjustment Building (Out House, Garages)

Safety ClearanceIf the distance with adjustment building is less than 3 mt and there is no any Road interval than GI pipe of suitable size shall be installed. This pipe shall be exposed on wall at height of not less than 2.5 mt.
Safety ClearanceIf the distance with adjustment building is more than 3 mt and there is any Road interval than GI pipe of suitable size shall be installed. This pipe shall be exposed on wall at height of not less than 4 mt.

Conduit

Metallic ConduitShall be used for Industrial wiring, Heavy mechanical Stress, shall be ISI marked, The Thickness shall not be less than 1.6mm(16SWG) for conduits up to 32mm Dia and not less than 2mm (14SWG) for conduit above 32mm Dia.
Metallic ConduitNo steel conduit less than 20 mm Diameter shall be used.
Metallic ConduitFor rigid Conduit IS:2509/IS:3419 and For Flexible Conduit IS:6946.
Metallic AccessoriesAll Metallic conduit accessories shall be threaded type (Not pin grip, clamp grip)
Metallic AccessoriesSaddle for surface conduit work on wall shall not less than 0.55mm(24 gauge) for conduit up to 25mm Dia not less than 0.9mm (20 gauge) for larger Dia
Metallic OutletsFore Cast Boxes:

Wall thickness shall be at least 3mm.                                                                                                

For Welded mild Steel Box:

Wall thickness shall not be less than 1.2mm (18 gauge) for Boxes up to size 20cmX30cm. Above This size 1.6mm(16guage)thick MS Boxes shall be used.

Metallic OutletsClear depth of Out less Box shall not be less than 60mm.

This will be increased as per mounting of Fan regulator

Bends in ConduitsBending radius not less than 7.5 cm
Fixating Conduits on SurfaceConduits shall be fixed by saddles not less than 1mt interval but in case of coupler/Bends in either side of saddles, The saddle shall be fitted 30 cm from fitting.
Non Metallic AccessoriesNormally grip Type.
Non Metallic Outlet(PVC Box)PVC Box IS:5133(PartII) thickness not less than 2mm,Clear depth of PVC Boxes not less than 60mm.
Non Metallic Surface ConduitConduits shall be fixed by saddles not less than 60cm interval but in case of coupler/Bends in either side of saddles, The saddle shall be fitted 15 cm from fitting.

Junction Box

Junction BoxDepth of Junction Box shall be min 65mm as per IS: 2667.

Fish Wire

Fish WireGI fish wire of 1.6mm/1.2mm (16SWG) shall be used.

Bus bar

Bus barBusbar shall be 100A,200A,300A,400A,500A,600A,800A
Bus barThe Cross-section area of Bus bar shall be same as Phase Bus bar (Up to 200A) for higher Capacity Neutral Bus bar must be not less than half cross section areas of Phase Bus bar.
Bus barBus bar shall be suitably installed with PVC sleeve/Tap.
Bus barBus bar Chamber shall be fabricated with MS angle for Frame work and sheet steel of thickness not less than 1.5mm.
Bus barMinimum clearance between phase to earth shall be 26mm and phase to phase shall be 32mm.

Bus bar Trucking

Bus bar Trucking Bus bar Trucking are generally used for interconnection between T/C over 500KVA/D.G set over 500KVA and their switch Board Panel.
Bus bar TruckingBus bar Trucking enclosure sheet steel of min 2mm thickness

Earthing

EarthingType of earthling are Pipe earthling/Plate earthling/Strip earthling.
EarthingLength of Buried strip shall not be less than 15mt.
EarthingTwo copper strip, each size 50mmX5mm shall be provided as each bus bar in 11KV S/S or D.G generally.
EarthingEach strip should be connected separately to earth.
EarthingTwo no of Body earthling of T/C,Panel,D.G are connected to earth Bus.
EarthingNeutral Leads of T/C,D.G shall not be connected to earth Bus.
EarthingThe minimum Cross-section are of protective conductor (Not contained within cable or wire) 2mm Dia(14SWG) for Copper, 2.5mm Dia(12SWG) for G.I, 2.24mm Dia(13SWG) for Aluminum.
EarthingEarthing Pit shall not be closer than 1.5mt from Building.
EarthingTop of Pipe earthling electrode shall not be less than 20cm below the ground
EarthingPlate electrode shall be buried in ground with face vertical and it’s Top not less than 3mt below ground level.
EarthingThe strip of earthling electrode shall be buried in trench not less than 0.5m deep.
EarthingIf strip electrode cannot be laid in straight length. It may be Zigzag with deviation up to 45 Degree from axis of strip.
EarthingIn Plate Earthing Dia of water pipe shall not be less than 20mm and in Pipe earthling reducer of 40mmX20mm shall be used.
EarthingEarthing Pit Size shall be not less than 30cmX30cmX30cm.
EarthingThickness of MS cover of earthling pit shall be not less than 6mm and having locking arrangements.
EarthingEarthing resistance of each electrode shall be less than 5Ω and for Rocky Soil not less than 8Ω
EarthingEarthing conduit for earthling wire shall be Medium class 15mm Dia GI pipe and for Earthing Strip shall be medium class 40mm Dia GI Pipe.

Conductor Clearance(min)

Cable crossingThe horizontal and vertical distance between Power and Communication cable shall not be less than 60cm.
Railway crossingAfter taking approval of railway authority, Cable under railway track shall be min 1mt from bottom of sleeper under RCC or cast Iron Pipe.
Railway crossingCable in parallel to Railway track shall be min 3mt far away from centre of nearest Track.
Cable Laying in PipeFor Single Conductor Shall be min 10cm Dia and more than Two Cable shall be min 15cm Dia.
Cable in Road CrossingIn Road Crossing Cable shall be laid min 1 mt below Road in Pipe.

Cable trench

Cable trenchFor single cable: For below 11Kv.Min length of Trench shall be 35cm and depth shall be min 75cm ( with sand cushioning of 8cm at bottom +Cable+ protective covering/Sand cushioning of 17cm above Cable) and without Cushioning Depth shall be 75cm+25cm.
Cable trenchFor single cable: For above 11Kv.Min length of Trench shall be 35cm and depth shall be min 1.2mt ( with sand cushioning and protective covering).
Cable trenchFor multi cable in horizontal level: Min distance between two cable shall be 20cm and min distance between cable and edge of trench on both side shall be 15cm
Cable trenchFor multi cable in Vertical level: Min distance between two cable shall be 30cm.(min Sand cushioning at bottom of trench shall be 8cm +Cable+min Sand cushioning of 30cm+Cable+protective covering/Sand cushioning of 17cm above Cable)
Cable trenchFor LV/MV cable cushioning is not required where there is no possibility of mechanical damages.
Cable trenchExtra loop of cable at end shall be 3mt for cable termination/Joints.

Cable Route

Cable Route MarkerCable Route Marker shall be min 0.5mt away from cable trench at the interval not exceeding 100mt parallel.
Cable Route MarkerPlate Type Cable Route Marker shall be made of 100mmX5mm GI/Aluminum Plate welded/Bolted on 35mmX35mmX6mm Iron angle of 60cm Long.
Cable Route MarkerCement Concrete(C.C) type marker shall be made in formation of 1:2:4.

Cable Bending Radius

Cable Bending RadiusVoltage      1Core          Unarmoured(Multi core)    Armoured(Multi core)                                                    11KV          20D                   15D                                        2D                                                                      22KV              20D                20D                                       15D 

 33KV              20D                25D                                      20D                                                   

Cable Tray (Perforated)

Cable Tray (Perforated)Cable Tray may be fabricated by two angle irons of 50mmX50mmX6mm as two longitudinal members with cross bracing between them 50mmX5mm welded/Bolted at angle and 1 mt spacing of 2mm thick MS sheet.

Overhead Line

Steel Tubular Pole1/6 length of Steel Tubular Pole + 30 cm from base shall be coated with Black Bituminous paint on both internally and externally.

The remaining portion of the pole shall be painted with Red oxide.

Cross armLV/MV Line: MS angle iron of size not less than  50mmX50mmX6mm(4.5kg/mt)                                                                 

11KV  Line: MS angle iron of size not less than 65mmX65mmX6mm(5kg/mt)

Cross armLV/MV Line: MS Chanel iron of size not less than 75mmX40mmX4.8mm(7.14kg/mt)

11KV  Line: MS Chanel iron of size not less than 75mmX40mmX4.8mm(7.14kg/mt) 

Cross armFor LV/MV Line:

Min distance shall be 5cm between centre of insulation pin and end of cross arm.                                    

For 11KV Line:

Min distance shall be 10cm between center of insulation pin and end of cross arm.  

Cross arm LengthVoltage        No of Horizontal Conductor        Length of Cross Arm                                                   LV/MV         2 Conductors                                   55cm                                                                              LV/MV          4 Conductors                                  115cm                                                                            LV/MV         4 Conductors Guard                         175 cm 

11KV            3 Conductors                                  225cm

StrutsThe Pit for Struts shall be located not less than 1.8mt from pole side. The depth of Pit shall be at least 1.2mt
Danger boardAll Support carrying HV Line shall be fitted with Danger Board( IS:2551) at height of 3mt.
Anti Climbing DeviceFor HV Line(IS:278-1978) having 4Point Barbs 75mm+12mm apart weight 128/125 gm/mt shall be wrapped helically with pitch of 75mm around Limb of Pole height of 3.5mt to 5 to 6 mt.
InsulatorFor LV/MV Overhead Line: Pin/Shackle Insulator and For 11KV Line Pin/Disc Insulator
InsulatorFor Pin Insulator for LV/MV line:

 Stalk Length 135mm Shank Length 125 mm , min Load 2KN.                                                                  For Pin Insulator for 11KV  line:

Stalk Length 165mm Shank Length 150 mm ,min Load 2KN.

D ClampD clamp shall be made of MS Flat size of 50mmX6mm,height of 75mm Galvanized and only used for vertical configuration for LV/MV Line only.
Pole Top ClampPole Top clamp made from Flat iron 50mmX8mm.
Stay wire RodStay wire Rod shall not be less than 1.8 m Long and 19mm Dia.Ankor Plate shall not be less than 45mmX45mmX7.5mm.
Overhead Conductor (min)For LV  Line :

AAC(All Alu.Cond) 7/1/2.21mm, ACSR 6/1/1/2.11mm, AAAC(All Alu.Alloy Cond) 7/2.09mm(20Sqmm)    

For 11KV/33KV   Line :

AAC(All Alu.Cond) N/A, ACSR 6/1/1/2.11mm, AAAC(All Alu.Alloy Cond) 7/2.56mm(30Sqmm)

Binding WireBinding Wire with insulator shall be with 2.6mm(12SWG) soft aluminum wire.
Earthing in Overhead LineEarthing wire shall not be less than 4mm(8SWG) and min 3 earthling Pit per KM shall be required.

 If there is no Continuous wire for earthling in overhead line than each pole should be earthed.

Overhead Line Conductor Clearance(min)

Same SupportFor LV/MV Line on Same Support Vertical distance:

Between Phase to Earth shall be min 30cm and

Between Phase to Phase min 20cm

Same SupportFor LV/MV Line on Same Support  Horizontal distance:

Between Live wire on either side of support shall be 45cm.

Same SupportFor LV/MV Line on Same Support  Horizontal distance:

Between Live wire on same side of support shall be 30cm.

Same SupportFor LV/MV Line on Same Support Horizontal distance:

 Between central of pin insulator to end of cross Arm shall be 05cm.

Same SupportFor HV Line In Triangular Configuration for 11KV/33KV Line shall be min 1.5mt.
Different VoltageWhen Two conductor of different Voltage are erected on same support min clearance between LV/MV and 11KV shall be min 1mt.
Different SupportA Clearance not less than height of tallest support may be maintained between parallel overhead line on Different support.
Different SupportWhen Two overhead line cross each other vertical clearance between LV/MV and 11KV shall not be less than 1.25mt and for LV/MV and 33KV line shall be not less than 2mt.
Across RoadMin Conductor Clearance across Road:

For LV/MV Line is 5.8mt and for HV Line 6.1mt

Along RoadMin Conductor Clearance along Road:

For LV/MV Line is 5.5mt and for HV Line 5.8mt

Along/AcrossMin Conductor Clearance along/across Road:

For LV/MV/HV up to 11Kv (Bare Cond) Line is 4.6mt.                                    

Min Conductor Clearance along/across Road:

For LV/MV/HV up to 11Kv (Insulated Cond) Line is 4.0mt.                            

Min Conductor Clearance along/across Road:

 For HV (11Kv To 33Kv) Line is 5.2mt.                                                          

Min Conductor Clearance along/across Road:

 For EHV (above 33Kv) is 5.2mt + 0.3 mt for every 33KV(Not Less than 6.1).

From BuildingMin Conductor Vertical Clearance above Building:

For LV/MV Line is 2.5mt from highest Point.                                            

Min Conductor Horizontal Clearance near Building:

For LV/MV Line is 1.5mt from nearest Point.                                        

Min Conductor Vertical Clearance above Building:

 For MV/EHV(up to 33KV)  Line is 3.7mt from highest Point.                                          

Min Conductor Vertical Clearance above Building:

 For MV/EHV(above 33KV)  Line is 3.7mt + 0.3mt for every 33KV                                                                                                                                                                 Min Conductor Horizontal Clearance above Building:

For MV/EHV(Up to 11KV)  Line is 1.2mt.                                             

Min Conductor Horizontal Clearance above Building:

For EHV(Up to  33KV)  Line is 02mt.                                                     

Min Conductor Horizontal Clearance above Building:

For EHV(above  33KV)  Line is 2mt + 0.3mt for every 33KV

Looping Box

Looping BoxLooping Bus shall be fabricated from MS Sheet of 1.6mm(16SWG) thickness, Min Size 250mmX200mmX100mm for single cable entry and for 250mmX300mmX100mm for more than two cable entry

Feeder Pillar

Feeder PillarFeeder Pillar shall be fabricated min 2mm thick MS sheet and hinged type double door at front side. If width of Pillar shall be less than 60cm than single hinged type door shall be permitted.
Feeder PillarMin height of Pedestal of Feeder Pillar shall be not less than 45cm and 1 to 2 mt height from Road Level.
Feeder PillarEach Feeder Pillar shall be earthed with 2 no of Earthing electrode.

Substation

Area of S/SS/S                TC Room Area      Total S.S Area(T.C,HT/LT Panel, without DG)                                      2X500KVA     36 Sq.meter            130 Sq.meter                                                                                       3X500KVA     54 Sqmeter             172 Sq.meter                                                                                           2X800KVA     39 Sqmeter             135 Sq.meter                                                                                       3X800KVA    58 Sqmeter             181 Sq.meter                                                                                        2X1000KVA   39 Sqmeter             149 Sq.meter                                                                                           2X1000KVA   58 Sqmeter             197 Sq.meter