Electrical Safety Clearance for Transformer

 

Electrical Safety Clearance for Transformer:

 Clearance from Outdoor Liquid Insulated Transformers to Buildings (NEC):

LiquidLiquid Volume (m3)Fire Resistant WallNon-Combustible WallCombustible WallVertical Distance
Less FlammableNA0.9 Meter0.9 Meter0.9 Meter0.9 Meter
<38 m31.5 Meter1.5 Meter7.6 Meter7.6 Meter
>38 m34.6 Meter4.6 Meter15.2 Meter15.2 Meter
Mineral Oil<1.9 m31.5 Meter4.6 Meter7.6 Meter7.6 Meter
1.9 m3 to 19 m34.6 Meter7.6 Meter15.2 Meter15.2 Meter
> 19 m37.6 Meter15.2 Meter30.5 Meter30.5 Meter

 Clearance between Two Outdoor Liquid Insulated Transformers (NEC):

LiquidLiquid Volume (m3)Distance
Less FlammableNA0.9 Meter
<38 m31.5 Meter
>38 m37.6 Meter
Mineral Oil<1.9 m31.5 Meter
1.9 m3 to 19 m37.6 Meter
> 19 m315.2 Meter

 Dry Type Transformer in Indoor Installation (NES 420.21):

Voltage

Distance  (min)
Up to 112.5 KVA300 mm (12 in.) from combustible material unless separated from the combustible material by a heat-insulated barrier.
Above 112.5 KVAInstalled in a transformer room of fire-resistant construction.
Above 112.5 KVA with Class 155 Insulationseparated from  a fire-resistant barrier not less than 1.83 m (6 ft) horizontally and 3.7 m (12 ft) vertically

 Dry Type Transformer in Outdoor Installation (NES 420.22):

Voltage

Distance  (min)
Above 112.5 KVA with Class 155 Insulationseparated from  a fire-resistant barrier not less than 1.83 m (6 ft) horizontally and 3.7 m (12 ft) vertically

 Non Flammable Liquid-Insulated Transformer in Indoor Installation (NES 420.21):

Voltage

Distance  (min)
Over 35KVInstalled indoors Vault (Having liquid confinement area and a pressure-relief vent for absorbing any gases generated by arcing inside the tank, the pressure-relief vent shall be connected to a chimney or flue that will carry such gases to an environmentally safe area
Above 112.5 KVAInstalled in a transformer room of fire-resistant construction.
Above 112.5 KVA (Class 155 Insulation)separated from  a fire-resistant barrier not less than 1.83 m (6 ft) horizontally and 3.7 m (12 ft) vertically

 Oil Insulated Transformer in Indoor Installation (NES 420.25):

Voltage

Distance  (min)

Up to 112.5 KVA

Installed indoors Vault (With construction of reinforced concrete that is not less than 100 mm (4 in.) thick.

Up to 10 KVA & Up to 600V

Vault shall not be required if suitable arrangements are made to prevent a transformer oil fire from igniting

Up to 75 KVA & Up to 600V

Vault shall not be required if where the surroundingStructure is classified as fire-resistant construction.
Furnace transformers (Up to 75 kVA)Installed without a vault in a building or room of fire resistant construction

 Transformer Clearance from Building (IEEE Stand):

Transformer

Distance from Building  (min)
Up to 75 KVA

3.0 Meter

75 KVA to 333 KVA

6.0 Meter

More than 333 KVA

9.0 Meter

 Transformer Clearance Specifications (Stand: Georgia Power Company):

Description of Clearance

Distance  (min)

Clearance in front of the transformer

3.0 Meter

Between Two pad mounted transformers (including Cooling fin)

2.1  Meter

Between Transformer and Trees, shrubs, vegetation( for unrestricted natural cooling )

3.0 Meter

The edge of the concrete transformer pad to nearest the building

4.2 Meter

The edge of the concrete transformer pad to nearest  building wall, windows, or other openings

3.0 Meter

Clearance from the transformer to edge of (or Canopy) building (3 or less stories)

3.0 Meter

Clearance in front of the transformer doors and on the left side of the transformer, looking at it from the front. (For operation of protective and switching devices on the unit.)

3.0 Meter

Gas service meter relief vents.

0.9 Meter

Fire sprinkler values, standpipes and fire hydrants

1.8 Meter

The water’s edge of a swimming pool or any body of water.

4.5 Meter

Facilities used to dispense hazardous liquids or gases

6.0 Meter

Facilities used to store hazardous liquids or gases

3.0 Meter

Clear vehicle passageway at all times, immediately adjacent of Transformer

3.6 Meter

Fire safety clearances can be reduced by building a suitable masonry fire barrier wall (2.7 Meter wide and 4.5 Meter Tall) 0.9 Meter from the back or side of the Pad Mounted Transformer  to the side of the combustible wall

 

Front of the transformer must face away from the building.

 

Clearance of Transformer-Cable-Overhead Line (Stand: Georgia Power Company):

Description of Clearance

Horizontal Distance (mm)

to pad-mounted transformers

to buried HV cable

to overhead HV Line

Fuel tanks

7.5 Meter

1.5 Meter

7.5 Meter

Granaries

6.0 Meter

0.6 Meter

15 Meter

Homes

6.0 Meter

0.6 Meter

15 Meter

Barns, sheds, garages

6.0 Meter

0.6 Meter

15 Meter

Water wells

1.5 Meter

1.5 Meter

15 Meter

Antennas

3.0 Meter

0.6 Meter

Height of Antenna + 3.0 Meter