Electrical Safety Clearance (ETSA Utilities,Australia) (Part-4)

 

Vertical Clearances between Services:

Service

LV Cable

HV Cable

Common Pipe

0.100 Meter

0.100 Meter

Gas Pipe

0.200 Meter0.200 Meter

Sewer Pipe

0.300 Meter0.300 Meter

Water Pipe

0.600 Meter0.600 Meter

 

 

 

 Horizontal Clearances between Services:

Service

LV Cable

HV Cable

Common Pipe

0.100 Meter

0.100 Meter

Gas Pipe

0.200 Meter0.200 Meter

Sewer Pipe

1.0 Meter1.0 Meter

Water Pipe

0.600 Meter0.600 Meter

 

 

 

 Standard: UK Power Networks – EI 02-0019

 Cable Installation Depths:

Voltage

Area

Depth (min)

Low Voltage

Footways, grass verges or private property

0.450 Meter

Carriageways (including road crossings)

0.600 Meter

Normal agricultural land (not deep ploughing)

1.0 Meter

Agricultural land subject to deep ploughing

1.2 Meter

11 KV to 20 KV

Footways, grass verges or private property

0.600 Meter

Carriageways (including road crossings)

0.750 Meter

Normal agricultural land (not deep ploughing)

1.0 Meter

Agricultural land subject to deep ploughing

1.2 Meter

33 KV to 132 KV

Footways, grass verges or private property

0.900 Meter

Carriageways (including road crossings)

0.900 Meter

Normal agricultural land (not deep ploughing)

1.0 Meter

Agricultural land subject to deep ploughing

1.2 Meter

Auxiliary Multi-core & Multi-pair Cables

Footways, grass verges or private property

0.450 Meter

Carriageways (including road crossings)

0.600 Meter

Normal agricultural land (not deep ploughing)

1.0 Meter

Agricultural land subject to deep ploughing

1.2 Meter

On Cable Ladder for LV to HVThe Horizontal clearance between cables on cable ladders

2X Dia of Cable of Largest Cable or min 150 mm

The clearance from a supporting wall

20 mm

The vertical clearance between cables is greater

150 mm

If the number of cables > 4, they are to be installed in a horizontal

 

 Minimum Approach Distance of Crane or Moving Part from Live Conductor:

Voltage

Without Safety Observation

For ordinary Person

Un insulated portions

Insulated portions

Upto1KV

2 Meter

1.0 Meter

3.0 Meter

11 KV

2 Meter

1.4 Meter

3.0 Meter

22 KV

2.4 Meter

2 Meter

3.0 Meter

33 KV

2.4 Meter

2 Meter

3.0 Meter

66 KV

2.8 Meter

2 Meter

3.0 Meter

132 KV

3.0 Meter

3.0 Meter

3.0 Meter

220 KV

4.8 Meter

4.8 Meter

6.0 Meter

330 KV

6.0 Meter

6.0 Meter

6.0 Meter

500 KV

8.0 Meter

8.0 Meter

8.0 Meter

 Minimum Fixed Clearances for Electrical Apparatus (Isolation Points):

Voltage

Fixed Clearance

Up to 11Kv

0.320 Meter

11KV to 33KV

0.320 Meter

33KV to 66KV

0.630 Meter

66KV to 132KV

1.1 Meter