Electrical Clearance in Substation

 Minimum Clearance in Substation:

VoltageHighest VoltageLighting Impulse Level (Kvp)Switching Impulse Level (Kvp)Minimum ClearanceSafety Clearance(Mt)Ground Clearance(Mt)
Phase-EarthPhase-Phase
11KV12KV70 0.1780.2292.6003.700
33KV36KV170 0.3200.3202.8003.700
132KV145KV550 1.1001.1003.7004.600
650 1.1001.1002.7004.600
220KV245KV950 1.9001.9004.3005.500
1050 1.9001.9004.3005.500
400KV420KV14251050(P-E)3.4004.2006.4008.000 

 Electrical Clearance in Substation:

VoltageHeight of I Bay From Ground (Mt)Height of II Bay From Ground (Mt)Bay Width (Mt)Phase-Phase (Mt)BetweenEquipmentEarth Wire From Ground
132KV (Single)8.011.03.03.010.5
220KV (Single)12.5184.54.515.5
220KV (Double)18.525254.54.528.5
400KV15.62222.07.0>6.030.0

Standard Bay Widths in Meters:

VoltageBay Width (Meter)
11KV4.7 Meter
33KV4.7 Meter
66KV7.6 Meter
132KV12.2 Meter
220KV17 Meter
400KV27 Meter

 Standard Bus and Equipment Elevation

VoltageEquipment live Terminal Elevation (Meter)Main BusTake of Elevation (Meter)
LowHigh
11 KV/33KV2.8To 45.5  To6.596.5To8.5
66KV2.8To 46To89To 10.59.5
132KV3.7To58To9.513.5To14.512To12.5
220KV4.9To5.59To1318.515To18.5
400KV8.015.523

 Phase spacing for strung Bus:

VoltageClearance
11KV1300 mm
33KV1300 mm
66KV2200 mm
132KV3000 mm
220KV4500 mm
400KV7000 mm

 Minimum Clearance of Live Parts from Ground:

VoltageMinimum Clearance to Ground (Mt)Section Clearance (Mt)
11KV3.7002.600
33KV3.7002.800
66KV4.6003.000
132KV4.6003.500
220KV5.5004.300
400KV8.0007.000

 Insulator String:

 VoltageNo of Suspension StringLength (mm)No of Disc for Tension StringLength in (mm)
66KV596561070
132KV91255101820
220KV141915152915
400KV2338502 X 235450

 Nominal Span:

VoltageNormal Span (Meter)
66KV240-250-275
132KV315-325-335
220KV315-325-335
400KV315-325-335

 Minimum Ground Clearance:

VoltageGround (Meter)
66KV5.5
132KV6.1
220KV7.0
400KV8.0
800KV12.4

 Indoor Substation Minimum Clearances

 

DistanceDescriptions
0.9 MeterHorizontally between any item of equipment and thesubstation wall
0.6 MeterHorizontally between any Two items of equipment
1.2 MeterHorizontally in front of any HV switchgear

 Clearance of Conductor on Tower

VoltageTower TypeVertical Space (Mt)Horizontal Space(Mt)Total Height From Ground(Mt)
66KVA1.034.015.91
 B1.034.2715.42
 C1.224.8816.24
132KVA7.1402.1723.14
 B4.26.2922.06
 C4.27.1522.68
 D4.28.824.06
220KVA5.28.528.55
 B5.2510.529.08
 C6.712.631.68
 D   

 NORMS OF PROTECTION FOR EHV CLASS POWER TRANSFORMERS

Voltage ratio & capacityHV SideLV SideCommon relays
 132/33/11KV up to 8 MVA  3 O/L relays + 1 E/L relay2 O/L relays + 1 E/L relayBuchholz, OLTC Buchholz, OT, WT
 132/33/11KV above 8 MVA and below 31.5 MVA  3 O/L relays + 1 dir. E/L relay3 O/L relays + 1 E/L relayDifferential, Buchholz, OLTC Buchholz, OT, WT
 132/33KV, 31.5 MVA & above  3 O/L relays + 1 dir. E/L relay3 O/L relays + 1 E/L relayDifferential, Over flux,Buchholz, OLTC PRV, OT, WT
 220/33 KV, 31.5MVA & 50MVA 220/132KV, 100 MVA  3 O/L relays + 1 dir. E/L relay3 O/L relays + 1 dir. relayDifferential, Over flux,Buchholz, OLTC PRV, OT, WT
 400/220KV 315MVA  3 directional O/L relays (with dir. High set) +1 directional E/L relays. Restricted E/F relay + 3 Directional O/L relays for action3 directional O/L relays (with dir. High set)+1 directional E/L relays. Restricted E/F relayDifferential, Over flux,Buchholz, OLTC PRV, OT, WT and overload (alarm) relay

 The bottom most portion of any insulator or bushing in service should be at a minimum height of 2500 mm above ground level.

 Location of L.A (From T.C Bushing):

VoltageBIL KV PeakDistance (Mt)
11KV7512
33KV20015
66KV32524
132KV55035
220KV900 To 1050Close To T.C
400KV1425 To 1550