Electrical Abstract-National Electrical Code-NEC

 

Capacitor Bank for Power Supply Voltage
System VoltageMinimum rating of capacitor bank
3.3 KV , 6.6KV75 Kvar
11 KV200 Kvar
22 KV400 Kvar
33 KV600 Kvar

 

Capacities of PVC conduits
Nominal conductor Size mm16 mm20 mm25 mm32 mm
Number of Cables (maximum)
1.0651930
1.5541524
2.5331117
422813
62610
1046
1634
2523
352

 

System Highest and Lower Voltage
Ref: NEC(India) :2011
System VoltageHighest VoltageLowest Voltage
240 V264 V216 V
415 V457 V374 V
3.3 kV3.6 kV3.0 kV
6.6 kV7.2 kV6.0 kV
11 kV12 kV10 kV
22 kV24 kV20 kV
33 kV36 kV30 kV
66 kV72.5 kV60 kV
66 kV72.5 kV60 kV
132 kV145 kV120 kV
220kV 245 kV200 kV
400 kV420 kV380 kV

 

Number of Points for Dwelling Unit
Ref: NEC(India) :2011
No.DescriptionArea for the Main Dwelling Unit (m2)
35 mm245 mm255 mm285 mm2140 mm2
1Light points7 No8 No10 No12 No17 No
2Ceiling fans Pont2 No3 No4 No5 No7 No
3Ceiling fans No’s2 No2 No3 No4 No5 No
46A Socket outlets2 No3 No4No5 No7 No
516A Socket outlets1 No2 No3 No4No
6Call-bell (buzzer)1 No1 No1 No

 

Recommended Schedule of Socket-Outlets
Ref: NEC(India) :2011
DescriptionNumber of Socket
6A Socket16A Socket
Bedroom21
Living room22
Kitchen12
Dining room21
Garage11
For refrigerator1
For air-conditioner1 for each
Verandah1 per 10mter21
Bathroom11

 

Power requirements of the building
Ref: NEC(India) :2011
Part of ElectricalInstallationPart of the Total Power Requirement in %DiversityFactor
Ventilation, heating (air-conditioning)45%1.0
Power plant (drives)52%0.65
Lighting30%0.95
Lifts20%1.0
Kitchen10%0.6
Laundry5%0.6

 

Lift Car Speed
Ref: NEC(India) :2011
OccupancyNo. of Floors ServedCar Speed   m/s
Office building4 to 50.5 to 0.75 m/sec
Office building6 to 120.75 to 1.5 m/sec
Shops and departmental stores13 to 20More than 1.5 m/sec
Passenger lifts for low and medium lodging houses0.5 m/sec
Hotels4 to 50.5 to 0.75 m/sec
Normal load carrying lifts2.0 to 2.5 m/sec
Hospital passenger Lift4 to 50.5 to 0.75 m/sec
Hospital passenger Lift13 to 20More than 1.5 m/sec
Hospital bed lifts (Short travel lifts insmall hospitals)0.25 m/sec
Hospital bed lifts (Normal)0.5 m/sec
Hospital bed lifts (Long travel lifts inGeneral hospitals) 0.6 to 1.5 m/sec

 

Capacitor Ratings at Rated Voltage
Ref: NEC(India) :2011
Motor Rating(Kw)Capacitor Rating in kVAR for Motor Speed
3 000rev/min1 500rev/min1 000rev/min750rev/min600rev/min500rev/min
2.25111.522.52.5
3.7222.53.544
5.7233.54.555.5
7.5344.55.566.5
11.24567.58.59
1556791112
18.767910.51314.5
22.57810121517
371112.516182325
57161721232932
75212326283540
102313336384555
150404245476067
187465053556876

 

:Maximum Current Demand for Motor:
Ref: NEC(India) :2011
Nature of supplySize of installationMaximum current demand
Single phaseor Three phaseUp to and including 0.75 kWSix times the full load current
Above 0.75 kW and up to 7.5 kWThree times the full load current
Above 7.5 kW up to and up to11 kWTwo times the full load current
Above 11 kWOne and half times the full load current

 

Rated Basic Insulation Level (BIL)
Ref: NEC(India) :2011
Nominal System Voltage (kV)Rated BIL (kVp)
33 KV170
22 KV125
11 KV75
6.6 KV60
3.3 KV40

 

Illumination Level
Ref: NEC(India) :2011
LocationIllumination Level (Lux)
Residence
Entrance / Hallways100
Living room300
Dining Room150
Bed Room (General)300
Bed Room (Dressing , Bed Heads)200
Kitchen200
Kitchen sink300
Bathroom100
Sewing700
Workshop200
Staircase100
Garage70
Study Room300
Office Building
Entrance hall / Reception150
Conference Room / Executive Office300
General Office Space300
Business Machinery Operation450
Drawing Office450
Corridors70
Stairs100
Lift landing150
Hospital Building
Reception & Waiting150
General ward100
Bed Side150
Toilet70
Stairs100
Operation Theatre (General)300
Operation Theatre (Operation Table)Special
Laboratories300
Radiology100
Causality150
Dispensaries300
Laundry200
Dry Cleaning200
Ironing300
General Office450
Kitchen200
Assembly & Concert Halls
Foyers100 to 150
Auditoria100 to 150
Platform450
Corridors70
Stairs100
Cinema Halls
Foyers150
Auditoria50
Corridors70
Stairs100
Theatres
Foyers150
Auditoria70
Corridors70
Stairs100
School / College Building
Assembly Halls 
General150
Examination center300
Platform300
Classes 
Desktop300
Blackboard200 to 300
Libraries 
Shelves70 to 150
Reading Room150 to 300
Reading Table300 to 700
Cataloguing150 to 300
General 
Office300
Staff Room150
Corridors70
Stairs100

 

Lamp’s Lumen Data
Rating (Watt)Life (Hours)Initial Lumens
Incandescent Lamp
601000870
1007501750
15020001740
20020002300
50020006500
Fluorescent Lamp
1870001120
2070001020
3670002800
4070002700
2X4070004000
Compact Fluorescent Lamp
510000220
77000380
117000560
137000680
157000810
1870001050
2370001500
2670001800
3270002400
Mercury Vapour Lamp
100180003700
175240008600
2502400012100
4002400022500
10002400057000
Metal Halide Lamp
50150003400
70150005600
100150009000
1501000013500
1751000015000
2501000020500
4002000036000
100012000110000
High Pressure Sodium Vapour Lamps
35160002250
50240004000
70240005800
100240009500
1502400016000
2502400027500
4002400047500
100024000140000
Pulse Start Metal Halide Lamp
50150003400
70150005600
100150009000
1501500015000
1751500017500
2001500021000
2501500026300
3202000034000
4002000044000
4502000050000

 

:Duty Type of Motor:
Ref: IS-325
Duty Type SymbolDuty TypeApplication
S1Continuous DutyPumps, Bowers, Compressors, Fans
S2Short Time DutySiren, Flood relief Gates
S3Intermittent Periodic DutyValve, Actuators, Wire drawing machine
S4Intermittent Periodic Duty with startingHoist, Cranes, Lifts, Escalators
S5Intermittent Periodic Duty with starting / BreakingHoist, Cranes (with electronics Breaks), Rolling mills
S6Continuous Duty with Intermittent Periodic DutyMachine tools, Conveyors
S7Continuous Duty with starting / BreakingMachine tools,
S8Continuous Duty with periodic load changesPole Channing Applications

 

Type of Distribution System
As per IEC 60364-3
Unearthed SystemEarthed System
ITTT / TN (TN-S,TN-C,TN-C-S)
First Letter (the neutral point in relation to earth):T= directly earthed neutral (from the French word Terre)I =unearthed or high impedance-earthed neutral (e.g. 2,000 Ω)
Second letter (Exposed conductive parts of the electrical installation in relation to earth):T =directly earthed exposed conductive partsN =exposed conductive parts directly connected to the neutral conductor