Earthing Strip /Wire / Pit Quick Reference (As per CPWD) (Part-2)

 

Earthing Strip for Sub-Station Equipment

CPWD-TABLE VIII

Type of InstallationEarth ElectrodeEarth Strip
Indoor sub-station with HT panel, Transformer capacity up to  1600  KVA, LT panel, D.G Set.Copper Plate25 x 5 mm Copper Strip
Indoor sub-station with HT  panel, Transformer  capacity  above  1600  KVA, LT panel, D.G SetCopper Plate32 x 5 mm Copper Strip
HT Outdoor sub-stationCopper Plate25 x 5 mm Copper Strip
LT Indoor sub-station with generatorCopper Plate25 x 5 mm Copper Strip
LT   switch   room   with Main   LT  D.BCopper Plate20 x 3 mm Copper Strip

 

Neutral Earthing of Transformers and Generators

CPWD-TABLE VIII

Type of InstallationEarth ElectrodeEarth Strip for Neutral
Transformer  of  capacity  up  to  1600 KVACopper Plate25 x 5 mm Copper strip
Transformer  of  capacity  above  1600  KVACopper Plate32 x 5 mm Copper strip
Generating set of all capacityCopper Plate26 x 5 mm Copper strip
Type of InstallationEarth ElectrodeEarth Strip for Neutral
Transformer  of  capacity  up  to  1600 KVACopper Plate25 x 5 mm Copper strip

 

Earthing Strip for Bus Trunking and Rising Main

CPWD-TABLE VIII

Type of InstallationMaterial of Main ConductorEarth Strip
Bus   trunking   up   to   2500   Amp   capacityCopper/ Aluminum2 No 25 x 5 mm Copper Strip
Bus   trunking   above   2500   Amp   capacityCopper/ Aluminum2 No 32 x 5 mm Copper Strip
Bus  trunking for  generating set and LT panelCopper/ Aluminum2 No 25 x 5 mm Copper Strip
Rising main up to 400 Amp capacityCopper/ Aluminum2 No 20 x 5 mm Copper Strip
Rising  main  above  400  Amp  and  up to 800 AmpCopper/ Aluminum2 No  20 x 3 mm Copper Strip

 

The Size of Earthing conductors

As per CPWD

Size of phase conductorSize of Earthing conductor of the same material as phase conductor
Up to 4 sq.mm.Same size as that of phase conductor
Above 4 sq.mm. up to 16 sq.mm.Same size as that of phase conductor
Above 16 sq.mm. up to 35 sq.mm.16 sq.mm.
Above 35 sq.mm.Half of the phase conductor

 

Materials and Sizes of Earth Electrodes

CPWD-TABLE IX

Type of ElectrodesMaterialSize
PipeGI medium class40 mm dia 4.50 m long (without any joint)
Plate(i) GI60 cm x 60 cm x 6 mm thick
(ii) Copper60 cm x 60 cm x 3 mm thick
Strip(i) GI100 sq. mm section
(ii) Copper40 sq. mm section
Conductor(i) Copper4 mm dia (8 SWG)
Note :  Galvanization of GI items shall conform to Class IV of IS 4736 : 1986.

 

Minimum Sizes of Earthing Conductors for Use Above Ground

CPWD- TABLE X

Material and ShapeMinimum Size
Round copper wire or copper clad steel wire6 mm diameter
Stranded copper wire50 sq. mm or (7/3.00 mm dia)
Copper strip20 mm x 3 mm
Galvanized iron strip20 mm x 3 mm
Round Aluminum wire8 mm diameter
Aluminum strip25 mm x 3 mm

 

Minimum Sizes of Earthing Conductors for Use Below Ground

CPWD- TABLE XI

Material and ShapeMinimum Size
Round copper wire or copper clad steel wire8 mm diameter
Copper strip32 mm x 6 mm
Round galvanized iron wire10 mm x 6 mm
Galvanized iron strip32 mm x 6 mm

 

Selection of Type of Earthing Electrodes

As per CPWD

Type of electrodeApplication
GI pipeInternal electrical installations like Distribution Board and Meter Boards (in residential quarters), feeder pillars and poles etc.
GI plate(i) For Fire Fighting pumps and water supply pumps.
(ii) Lightning conductors.
Copper plateNeutral earthing of transformers/ generating sets.
Strip/ ConductorLocations where it is not possible to use other types.

 

Number of Earth Electrodes

As per CPWD

EquipmentNo of Earthing
For neutral earthing of each transformer2 sets
For body earthing of all the transformers,2 sets
HT/LT Panels and other electrical equipment
in the Sub-station/ power house
For neutral earthing of each generating set2 sets
For body earthing of all the generating sets,2 sets
LT panels, other electrical equipment in the generator room

 

Size of protective conductor

As per CPWD

Size of phase conductorSize of protective conductor of the same material as phase conductor
Up to 16 sq.mm.Same as Phase Conductor  Size
16 to 35 sq.mm.16 sq.mm.
35 sq.mmHalf Size of Phase Conductor

 

Earthing Points

As per CPWD

EarthingDescription
Location for Earth ElectrodesNormally  an  earth  electrode  shall  not  be  located  closer  than  1.5  m  from  any  building.
Installation of PipePipe electrode shall be buried in the ground vertically with its top at not less than 20 cm below the ground level
Installation of PlatePlate electrode shall be buried in ground with its faces vertical, and its top not less than 3.0 m below the ground level.
The strip or conductorThe strip or conductor electrode shall be buried in trench not less than 0.5 m  deep
More Earthing ElectrodeWhen more than one electrode (plate/pipe) is to be installed, a separation of not less than 2 m shall be maintained between two adjacent electrodes.
Earthing Electrode If the electrode cannot be laid in a straight length, it may be laid in a zigzag manner with a deviation upto 45 degrees from the axis of the strip. It can also be laid in the form of an arc with curvature more than 1 m or a polygon
Earthing Pit CoverA cast iron / MS frame with MS cover, 6 mm thick, and having locking arrangement shall be suitably embedded in the masonry enclosure.
Earthing Wire Protection The  earthing  conductor  from  the  electrode  up  to  the  building  shall  be  protected  from mechanical injury by a medium class, 15 mm dia. GI pipe in the case of wire, and by 40 mm dia, medium class GI pipe in the case of strip. The protection pipe in ground shall be buried at least 30 cm deep (to be increased to 60 cm in case of road crossing and pavements)
No of Earthing ConductorTwo protective conductors shall be provided for a switchboard carrying a 3-phase switch gear there on.
Earthing Electrode No earth electrode shall have a greater ohmic resistance than 5 ohms as measured by an approved earth testing apparatus. In rocky soil the resistance may be up to 8 ohms.
Earthing ResistanceEach   of   the   earth   stations   should   have   a   resistance   not   exceeding   the product  given  by  10  ohms  multiplied  by  the number  of  earth  electrodes  to be  provided  therein.  The  whole  of  the  lightning  protective  system,  including any  ring  earth, should  have  a  combined  resistance  to  earth  not  exceeding 
10 ohms without taking account of any bonding
More Earthing ResistanceIf the value obtained for the whole of the lightning protection system exceeds 10 ohms, a reduction can be achieved by extending or adding to the electrodes, or by  interconnecting  the  individual  earth  terminations  of  the  down  conductors  by  a  conductor